46 C.F.R. § 161.002-6

Current through November 30, 2024
Section 161.002-6 - Testing requirements
(a) Devices must be tested and listed for fire service by an accepted independent laboratory, as accepted in accordance with § 159.010 of this subchapter, or by a NRTL as set forth in 29 CFR 1910.7 .
(b) Each fire detection device must comply with the following standards (incorporated by reference, see § 161.002-1 ) as appropriate:
(1) Control units-UL 864;
(2) Heat detectors-UL 521;
(3) Smoke detectors-UL 268;
(4) Flame detectors-ANSI/FM 3260;
(5) Audible alarms-UL 464 or UL 1480;
(6) Visual alarms-UL 1971; and
(7) Manual Signaling Boxes-UL 38.
(c) All devices must be tested by an accepted independent laboratory, as defined in § 159.010 of this subchapter, to meet the marine environment testing requirements in Table 161.002-6(c) of this section. The test parameters are found in IEC 60092-504 (incorporated by reference, see § 161.002-1 ).

Table 161.002-6(c)-Marine Environmental Testing Requirements

IEC 60092-504 Environmental type test Category 1 Category 2 Category 3
All spaces not Category 2 or 3 Open deck or open to weather Spaces containing navigation or communication equipment
1-Visual inspectionXXX
2-Functional testXXX
3-High voltage testXXX
4a-Power supply variationsXXX
4b-Power supply failureXXX
5-Insulation resistanceXXX
6-Cold with gradual temp. changeX (5 °C)X (-25 °C)X (5 °C)
7-Dry heat with gradual temp. changeX (55 °C)X (55 °C)X (55 °C)
8-Damp heat, cyclicXXX
9-Salt mistX
10-Vibration (sinusoidal)XXX
11b-Inclination, dynamic1 X1 X1 X
13-Electrostatic dischargeXXX
14-Electromagnetic fieldXXX
15-Conducted low frequencyXXX
16(a)-Conducted radio frequency (3 V rms)X
16(b)-Conducted radio frequency (10 V rms)XX
17-Burst/fast transientsXXX
18-Surge/slow transientsXXX
19(a)-Radiated emission (general power)X
19(b)-Radiated emission (bridge and deck zone)XX
20(a)-Conducted emission (general power)X
20(b)-Conducted emission (bridge and deck zone)XX

1 This test only needs to be completed if the device is in a location with moving mechanical parts.

(d) All fire detection system control units and remote annunciators must have enclosure protection as outlined in part 5 of IEC 60092-504 (incorporated by reference, see § 161.002-1 ) if the requirements exceed those of 46 CFR 111.01-9 . Otherwise, 46 CFR 111.01-9 must be complied with.

46 C.F.R. §161.002-6

USCG-2012-0196, 81 FR 48275 , July 22, 2016
81 FR 48275 , 8/22/2016