Section 154.1115 - Discharge(a) The discharge density of each water spray system must be at least:(1) 10000 cm3/m2/min. (0.25 gpm/ft.2) over each horizontal surface; and(2) 4000 cm3/m2/min. (0.10 gpm/ft.2) against vertical surface, including the water rundown.(b) The water spray protection under § 154.1110 (d) and (e) must cover an area in a horizontal plane extending at least 0.5 m (19 in.) in each direction from the pipes, fittings, and valves, or the area of the drip tray, whichever is greater.