46 C.F.R. § 154.1160

Current through November 30, 2024
Section 154.1160 - Monitor coverage of system

The coverage of each dry chemical system monitor under § 154.1150 must not exceed:

(a) 10 m (32.8 ft.) at 10 kg/sec (22 lb/sec);
(b) 30 m (98.4 ft.) at 25 kg/sec (55 lb/sec);
(c) 40 m (131.2 ft.) at 45 kg/sec (99 lb/sec);
(d) An interpolation between 10 m (32.8 ft.) at 10 kg/sec (22 lb/sec) and 30 m (98.4 ft.) at 25 kg/sec (55 lb/sec); or
(e) An interpolation between 30 m (98.4 ft.) at 25 kg/sec (55 lb/sec) and 40 m (131.2 ft.) at 45 kg/sec (99 lb/sec).

46 C.F.R. §154.1160