46 C.F.R. § 153.407

Current through September 30, 2024
Section 153.407 - Special requirements for sounding tube gauges
(a) A sounding tube installed as a restricted gauge must extend to within one meter (approx. 39.4 in.) of the bottom of the tank.
(b) A sounding tube must not be installed on a tank whose relief valve setting exceeds 28 kPa (approx. 4 psig) unless it is specifically permitted by the Commandant (CG-ENG).
(c) A sounding tube must have no perforations in the tube wall.

46 C.F.R. §153.407

CGD 73-96, 42 FR 49027, Sept. 26, 1977, as amended by CGD 82-063b, 48 FR 4782, Feb. 3, 1983