46 C.F.R. § 111.51-5

Current through November 30, 2024
Section 111.51-5 - Protection of vital equipment
(a) The coordination of overcurrent protective devices must be demonstrated for all potential plant configurations.
(b) Protective relays and overcurrent protective devices must be installed so that:
(1) A short-circuit on a circuit that is not vital to the propulsion, control, or safety of the vessel does not trip equipment that is vital; and
(2) A short-circuit on a circuit that is vital to the propulsion, control, or safety of the vessel is cleared only by the protective device that is closest to the point of the short-circuit.

46 C.F.R. §111.51-5