46 C.F.R. § 111.30-24

Current through November 30, 2024
Section 111.30-24 - Generation systems greater than 3000 kW

Except on a non-self-propelled mobile offshore drilling unit (MODU) and a non-self-propelled floating Outer Continental Shelf facility, when the total installed electric power of the ship's service generation system is more than 3000 kW, the switchboard must have the following:

(a) At least two sections of the main bus that are connected by:
(1) A non-automatic circuit breaker;
(2) A disconnect switch; or
(3) Removable links.
(b) As far as practicable, the connection of generators and duplicated equipment equalized between the sections of the main bus.

46 C.F.R. §111.30-24

CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by CGD 94-108, 61 FR 28279, June 4, 1996
88 FR 16361 , 4/17/2023