Current through September 30, 2024
Section 111.107-1 - Industrial systems(a) For the purpose of this subpart, an industrial system is a system that-(1) Is not a ship's service load, as defined in § 110.15-1 ;(2) Is used only for the industrial function of the vessel;(3) Is not connected to the emergency power source; and(4) Does not have specific requirements addressed elsewhere in this subchapter.(b) An industrial system that meets the applicable requirements of NFPA 70 (incorporated by reference; see § 110.10-1 of this subchapter) must meet only the following: (1) Part 110, subpart 110.25, of this chapter-Plan Submittal.(2) Subpart 111.01 of this part-General.(3) Subpart 111.05 of this part-Equipment Ground, Ground Detection, and Grounded Systems.(4) Sections 111.12-1(b) and 111.12-1(c) -Prime movers.(5) Sections 111.30-1 , 111.30-5(a) , and 111.30-19(a) -Switchgear.(6) Subpart 111.105 of this part-Hazardous Locations.(c) Cables that penetrate a watertight or fire boundary deck or bulkhead must- (1) Be installed in accordance with 46 CFR 111.60-5 and meet the flammability-test requirements of either IEEE 1202, IEC 60332-3-22:2018, or IEC 60332-3-21:2018, Category A or A F/R (all incorporated by reference; see § 110.10-1 of this subchapter); or(2) Be specialty cable installed in accordance with § 111.60-2 .CGD 94-108, 61 FR 28286, June 4, 1996, as amended at 62 FR 23910, May 1, 1997; USCG-2003-16630, 73 FR 65201, Oct. 31, 2008