46 C.F.R. § 111.05-37

Current through November 30, 2024
Section 111.05-37 - Overcurrent devices
(a) A permanently grounded conductor must not have an overcurrent device unless the overcurrent device simultaneously opens each ungrounded conductor of the circuit.
(b) The neutral conductor of the emergency-main switchboard bus-tie must not have a switch or circuit breaker.

46 C.F.R. §111.05-37

CGD 94-108, 61 FR 28276, June 4, 1996