Table 111.05-31(b)-Neutral Grounding Conductor for Alternating-Current System
Size of the largest generator cable or equivalent for parallel generators-AWG-MCM (mm2) | Size of the system grounding conductor-AWG(mm2) | |
Greater than | Less than or equal to | |
2 (33.6) | 8 (8.4) | |
2 (33.6) | 0 (53.5) | 6 (13.3) |
0 (53.5) | 3/0 (85.0) | 4 (21.2) |
3/0 (85.0) | 350 MCM (177) | 2 (33.6) |
350 MCM (177) | 600 MCM (304) | 0 (53.5) |
600 MCM (304) | 1100 MCM (557) | 2/0 (67.5) |
1100 MCM (557) | 3/0 (85.0) |
46 C.F.R. §111.05-31