46 C.F.R. § 111.05-25

Current through November 30, 2024
Section 111.05-25 - Ungrounded systems

Each ungrounded system must be provided with a suitably sensitive ground detection system located at the respective switchboard which provides continuous indication of circuit status to ground with a provision to momentarily remove the indicating device from the reference ground.

46 C.F.R. §111.05-25

CGD 94-108, 61 FR 28276, June 4, 1996