Current through September 30, 2024
Section 98.30-37 - Firefighting requirementsNo person may lift a portable tank on or off a vessel, or transfer a product with a flashpoint of less than 300 °F to or from a portable tank or IBC unless-
(a) Water pressure is maintained on the firemain;(b) Firehoses, fitted with a Coast Guard-approved combination nozzle, are attached to each fire hydrant in the vicinity of the portable tanks;(c) Except as provided in § 98.30-39 , fire extinguishers of a dry chemical type are-(1) Located to protect the deck area 10 feet in any horizontal direction from each portable tank and its associated cargo handling system;(2) Coast Guard approved; and(3) Capable of covering the deck area without being moved;(d) In a deck area of 500 square feet or less, there are two or more dry chemical fire extinguishers of 300 pounds or more total capacity of extinguishing agent; and(e) In a deck area of more than 500 square feet, there are three or more dry chemical fire extinguishers of 450 pounds or more total capacity of extinguishing agent.CGD 73-172, 39 FR 22954, June 25, 1974, as amended by USCG-2011-0088, 78 FR 54787, Sept. 6, 2013