46 C.F.R. § 98.30-37

Current through September 30, 2024
Section 98.30-37 - Firefighting requirements

No person may lift a portable tank on or off a vessel, or transfer a product with a flashpoint of less than 300 °F to or from a portable tank or IBC unless-

(a) Water pressure is maintained on the firemain;
(b) Firehoses, fitted with a Coast Guard-approved combination nozzle, are attached to each fire hydrant in the vicinity of the portable tanks;
(c) Except as provided in § 98.30-39 , fire extinguishers of a dry chemical type are-
(1) Located to protect the deck area 10 feet in any horizontal direction from each portable tank and its associated cargo handling system;
(2) Coast Guard approved; and
(3) Capable of covering the deck area without being moved;
(d) In a deck area of 500 square feet or less, there are two or more dry chemical fire extinguishers of 300 pounds or more total capacity of extinguishing agent; and
(e) In a deck area of more than 500 square feet, there are three or more dry chemical fire extinguishers of 450 pounds or more total capacity of extinguishing agent.

46 C.F.R. §98.30-37

CGD 73-172, 39 FR 22954, June 25, 1974, as amended by USCG-2011-0088, 78 FR 54787, Sept. 6, 2013