Section 98.30-21 - Inspection prior to transferNo person may transfer to or from a portable tank or IBC a product with a flashpoint of less than 300 °F unless the person in charge of the transfer determines that-
(a) Each warning signal and sign required in §§ 98.30-33 and 98.30-35 is displayed;(b) No repair work in the vicinity of any portable tank or IBC is done without permission of the person in charge of the transfer operation; and(c) Riveting, welding, burning, or a similar operation is not done in the vicinity of a portable tank or IBC unless an inspection by the person in charge of the transfer ensures that the operation can be done safely.CGD 73-172, 39 FR 22954, June 25, 1974, as amended by USCG-2011-0088, 78 FR 54787, Sept. 6, 2013