46 C.F.R. § 95.50-10

Current through September 30, 2024
Section 95.50-10 - [Effective until 10/18/2024] Location
(a) Approved portable fire extinguishers and semi-portable fire extinguishing systems must be installed in accordance with Table 95.50-10(a) of this section. The location of the equipment must be to the satisfaction of the Officer in Charge, Marine Inspection. Nothing in this paragraph should be construed as limiting the Officer in Charge, Marine Inspection, from requiring such additional equipment as he or she deems necessary for the proper protection of the vessel.
(b) Table 95.50-10(a) indicates the minimum required number and type of extinguisher for each space listed. Extinguishers with larger numerical ratings or multiple letter designations may be used if the extinguishers meet the requirements of the table.

Table 95.50-10(a)-Portable Fire Extinguisher and Semi-Portable Fire Extinguishing Systems

Space Minimum required rating Quantity and location
Safety Areas1
Wheelhouse or fire control roomNone required.
Stairway and elevator enclosuresNone required.
Communicating corridors.2-A1 in each main corridor not more than 150 ft apart. (May be located in stairways.)
Lifeboat embarkation and lowering stationsNone.
Radio room20-B:C22 required in the vicinity of the exit.2
Accommodations1
Staterooms, toilet spaces, public spaces, offices, lockers, isolated storerooms, pantries, open decks, etcNone required.
Service Spaces1
Galleys40-B:C1 for each 2,500 sq ft or fraction thereof suitable for hazards involved.
Paint and lamp rooms40-B1 outside space in the vicinity of the exit.
Accessible baggage, mail, specie rooms, and storerooms2-A1 for each 2,500 sq ft or fraction thereof located in the vicinity of the exits, either inside or outside the spaces.
Carpenter shop and similar spaces2-A1 outside the space in the vicinity of the exit.
Machinery Spaces
Coal-fired boilers: Bunker and boiler spaceNone required.
Oil-fired boilers: Spaces containing oil-fired boilers, either main or auxiliary, or their fuel-oil units40-B
160-B
2 required.3
1 required.4
Internal combustion or gas turbine propelling machinery spaces40-B1 for each 1,000 brake horsepower; not less than 2 but not more than 6.5
120-B1 required.6 7
Electric propulsive motors or generators of an open type40-B:C1 for each propulsion motor or generator unit.
Enclosed ventilating systems for motors and generators of electric propelling machineryNone required.
Auxiliary Spaces
Internal combustion or gas turbine40-B1 outside the space in the vicinity of the exit.7
Electric emergency motors or generators40-B:C1 outside the space in the vicinity of the exit.8
SteamNone required.
Trunks to machinery spacesNone required.
Fuel tanksNone required.
Cargo Spaces
Inaccessible during voyage, including trunks and cargo tanksNone required.
Accessible during voyageNone required.
Spare Units
2-A10 percent of the total number required rounded up.
40-B:C10 percent of the total number required rounded up.
20-B:C1

1 For motorboats, the total number of portable fire extinguishers required for safety areas, accommodation spaces, and service spaces must be one 20-B for motorboats of less than 50 GT and two 20-B ratings for motorboats of 50 GT or more.

2 For vessels on an international voyage, substitute one 20-C in the vicinity of the exit.

3 Vessels of less than 1,000 gross tons require one.

4 Vessels of less than 1,000 gross tons may substitute one 160-B.

5 Only one is required for motorboats.

6 If an oil-burning donkey boiler fitted in space, the 160-B previously required for the protection of the boiler may be substituted. Not required where a fixed carbon dioxide system is installed.

7 Not required on vessels of less than 300 gross tons if the fuel has a flashpoint higher than 110 °F.

8 Not required on vessels of less than 300 gross tons.

(c) Semi-portable fire extinguishing systems must be located in the open so as to be readily seen.
(d) If portable fire extinguishers are not located in the open or behind glass so that they may be readily seen, they may be placed in enclosures together with the firehose, provided such enclosures are marked as required by § 97.37-15 of this subchapter.
(e) Portable fire extinguishers and their stations must be numbered in accordance with § 97.37-23 of this subchapter.
(f) Portable or semi-portable extinguishers, which are required on their nameplates to be protected from freezing, must not be located where freezing temperatures may be expected.

46 C.F.R. §95.50-10

USCG-2012-0196, 81 FR 48264, July 22, 2016
81 FR 48264, 8/22/2016