46 C.F.R. § 108.411

Current through November 30, 2024
Section 108.411 - Smoke detection system

Each smoke accumulator in a smoke detection system must be located on the overhead of the compartment protected by the system in a location-

(a) Where no portion of the overhead of the compartment is more than 12 meters (40 feet) from an accumulator;
(b) That is no closer to the opening of a ventilator than 3 times the diameter or equivalent size of the opening.
(c) Where damage to the accumulator is unlikely to occur if it is not protected.

46 C.F.R. § 108.411