46 C.F.R. § 108.495

Current through September 30, 2024
Section 108.495 - [Effective 10/18/2024] Locations and number of fire extinguishers required

Table 1 to § 108.495 indicates the minimum required number and type of fire extinguishers for each space listed. Extinguishers with larger numerical ratings or multiple letter designations may be used if the extinguishers meet the requirements of the table.

Table 1 to § 108.495 -Carriage of Portable Fire Extinguishers

Space Minimum required ratingQuantity and location
Safety Areas
Wheelhouse and control room20-B:C2 in the vicinity of the exit.
Stairway and elevator enclosureNone required.
Corridors2-A1 in each corridor not more than 150 ft (45 m) apart. (May be located in stairways.)
Lifeboat embarkation and lowering stationsNone required.
Radio room 10-B:C2 in the vicinity of the exit.
Accommodations
Staterooms, toilet spaces, public spaces, offices, lockers, small storerooms, pantries, open decks, and similar spacesNone required.
Service Spaces
Galleys40-B:C1 for each 2,500 sq ft (232.2 sq m) or fraction thereof suitable for the hazards involved.
Paint and lamp rooms40:B1 outside each room in the vicinity of the exit.
Storerooms2-A1 for each 2,500 sq ft (232.2 sq m) or fraction thereof located in the vicinity of the exits, either inside or outside the spaces.
Workshop and similar spaces 20-B:C1 outside each space in the vicinity of the exit.
Machinery Spaces
Oil-fired boilers: Spaces containing oil-fired boilers, either main or auxiliary, or their fuel oil units40-B2 required in each space.
160-B1 required in each space. See note 1.
Internal combustion or gas turbine propelling machinery spaces40-B1 for each 1,000 brake horsepower but not less than 2 and not more than 6 in each space.
120-B1 required in each space. See note 1.
Motors or generators of electric propelling machinery that do not have an enclosed ventilating system40-B:C1 for each motor or generator.
Motors and generators of electric propelling machinery that have enclosed ventilating systemsNone required.
Auxiliary Spaces
Internal combustion engines or gas turbine40-B1 outside the space containing engines or turbines in the vicinity of the exit.
Electric emergency motors or generators40-B:C1 outside the space containing motors or generators in the vicinity of the exit.
Steam driven auxiliary machineryNone required.
Trunks to machinery spacesNone required.
Fuel tanksNone required.
Miscellaneous Areas
Helicopter landing decks160-B1 at each access route.
Helicopter fueling facilities160-B1 at each fuel transfer facility. See note 2.
Drill floor40-B:C2 required.
Cranes with internal combustion engines 40-B:C1 required.
Spare Units
2-A10 percent of the total required rounded up.
40-B:C10 percent of the total required rounded up.

1 Not required where a fixed gas extinguishing system is installed.

2 Not required where a fixed foam system is installed in accordance with § 108.489 .

46 C.F.R. §108.495

USCG-2012-0196, 81 FR 48266, July 22, 2016
81 FR 48266, 8/22/2016; 89 FR 76699, 10/18/2024