46 C.F.R. § 108.467

Current through November 30, 2024
Section 108.467 - Water supply

The water supply of a foam extinguishing system must not be the water supply of the fire main system on the unit unless when both systems are operated simultaneously-

(a) The water supply rate to the foam production equipment meets the requirements of this section; and
(b) Water supply rate to the fire hydrants required by § 108.415 of this subpart allows compliance with the pressure requirement in that section.

46 C.F.R. § 108.467