Installations contracted for on or after November 19, 1952 and prior to July 22, 2021, must meet the following requirements:
Table 76.27-80-Installations
Space | Detecting systems |
Safety Areas | |
Wheelhouse or fire-control room | None required.1 |
Stairway and elevator enclosures | None required.1 |
Communication corridors | None required.1 |
Lifeboat embarkation and lowering stations | None required. |
Radio room | None required.1 |
Accommodations | |
Staterooms, toilet spaces, isolated pantries, etc | None required.1 |
Offices, lockers, and isolated storerooms | Electric, pneumatic, or automatic sprinkling.1 |
Public spaces | None required with 20-minute patrol. Electric, pneumatic, or automatic sprinkling with 1 hour patrol.1 |
Open decks or enclosed promenades | None required. |
Service Spaces | |
Galleys | None required.1 |
Main pantries | None required.1 |
Motion picture booths and film lockers | Electric, pneumatic, or automatic sprinkling.12 |
Paint and lamp rooms | Smoke detecting.3 |
Inaccessible baggage, mail, and specie rooms and storerooms | Smoke detecting.3 |
Accessible baggage, mail, and specie rooms and storerooms | Electric, pneumatic, or automatic sprinkling. |
Refrigerated storerooms | None required. |
Carpenter, valet, photographic, and printing shops, sales rooms, etc | Electric, pneumatic, or automatic sprinkling. |
Machinery Spaces | |
Coal fired boilers: Bunker and boiler space | None required. |
Oil fired boilers: Spaces containing oil fired boilers either main or auxiliary, their fuel oil service pumps, and/or such other fuel oil units as the heaters, strainers, valves, manifolds, etc., that are subject to the discharge pressure of the fuel oil service pumps, together with adjacent spaces to which oil can drain | None required. |
Internal combustion or gas turbine propelling machinery spaces | None required. |
Electric propulsive motors or generators of open type | None required. |
Enclosed ventilating systems for motors and generators of electric propelling machinery | None required. |
Auxiliary spaces, internal combustion or gas turbine | None required. |
Auxiliary spaces, electric motors or generators | None required. |
Auxiliary spaces, steam | None required. |
Trunks to machinery spaces | None required. |
Fuel tanks | None required. |
Cargo Spaces | |
Inaccessible during voyage (combustible cargo), including trunks (excluding tanks) | Smoke detecting. |
Accessible during voyage (combustible cargo) | Smoke detecting, electric, pneumatic or automatic sprinkling. |
Vehicular deck (except where no overhead deck is 30 feet (9.14 meters) in length or less) | None required. |
Cargo oil tanks | None required. |
Specially suitable for vehicles | Smoke detecting, electric, pneumatic or automatic sprinkling. |
1 Vessels of 100 GT or more contracted for on or before May 27, 1936, and having combustible joiner work must be fitted with an automatic sprinkler system, except in relatively incombustible spaces.
2 Sprinkler heads may be attached to a sanitary system provided electrical or pneumatic detecting is installed.
3 On vessels contracted for prior to January 1, 1962, a steam smothering system may be accepted. However, although existing steam smothering systems may be repaired, replaced, or extended, no new system contracted for on or after January 1, 1962, will be permitted.
46 C.F.R. §76.27-80