Table 1 to § 61.05-10 -Inspection Intervals for Boilers 1
23
Firetube boiler [GREATER THAN EQUAL TO]150 psi | Watertube boiler | Any firetube boiler for propulsion | Firetube boiler <150 psi | |
Hydro Test: | ||||
Passenger Vessel | 2.5 | 2.5 | 1 | 2.5 |
Other Vessel | 2.5 | 5 | 1 | 5 |
Fireside Inspection | 1 | 2.5 | 1 | 2.5 |
Waterside Inspection | 1 | 2.5 | 1 | 2.5 |
Boiler Safety-Valve Test | 1 | 2.5 | 1 | 1 |
Valves Inspection | 5 | 5 | 5 | 5 |
Studs and Bolts Inspection | 10 | 10 | 10 | 10 |
Mountings Inspection | 10 | 10 | 10 | 10 |
Steam Gauge Test | 2.5 | 2.5 | 2.5 | 2.5 |
Fusible Plug Inspection | 2.5 | 2.5 | 2.5 |
1 All intervals are in years.
2 Where the 2.5-year interval is indicated: two tests or inspections must occur within any five-year period, and no more than three years may elapse between any test or inspection and its immediate predecessor.
3 Intervals for hybrid boilers are the same as for firetube boilers.
46 C.F.R. §§61.05-10