46 C.F.R. § 58.01-25

Current through September 30, 2024
Section 58.01-25 - Means of stopping machinery

Machinery driving forced-draft and induced-draft fans, fuel-oil transfer pumps, fuel-oil unit and service pumps, and similar fuel-oil pumps must be fitted with remote controls from a readily accessible position outside the space concerned so that the fans or pumps may be stopped in case of fire in the compartment in which they are located. The controls must be suitably protected against accidental operation and against tampering and must be suitably marked.

46 C.F.R. §58.01-25

CGD 83-043, 60 FR 24775, May 10, 1995