Table 28.160-Portable Fire Extinguishers for Vessels 65 Feet (19.8 Meters) or More in Length
Space | Minimum required rating | Quantity and location |
Safety areas, communicating corridors | 2-A | 1 in each main corridor not more than 150 ft (45.7m) apart. (May be located in stairways.) |
Pilothouse | 20-B:C | 2 in the vicinity of the exit. |
Service spaces, galleys | 40-B:C | 1 for each 2,500 sq ft (232.2 sq m) or fraction thereof suitable for hazards involved. |
Paint lockers | 40-B | 1 outside space in the vicinity of the exit. |
Accessible baggage and storerooms | 2-A | 1 for each 2,500 sq ft (232.2 sq m) or fraction thereof located in the vicinity of the exits, either inside or outside the spaces. |
Workshops and similar spaces | 2-A | 1 outside the space in the vicinity of the exit. |
Machinery spaces; Internal combustion propelling machinery | 40-B:C | 1 for each 1,000 brake horsepower or fraction thereof but not fewer than 2 or more than 6. |
Electric propulsion motors or generator unit of open type | 40-B:C | 1 for each propulsion motor generator unit. |
Auxiliary spaces | 40-B:C | 1 outside the space in the vicinity of the exit. |
Internal combustion machinery | 40-B:C | 1 outside the space in the vicinity of the exit. |
Electric emergency motors or generators | 40-B:C | 1 outside the space in the vicinity of the exit. |
46 C.F.R. §28.160