40 C.F.R. § 60 app Table 6 to Subpart IIII of Part 60

Current through October 31, 2024
Appendix Table 6 to Subpart IIII of Part 60 - Optional 3-Mode Test Cycle for Stationary Fire Pump Engines

[As stated in § 60.4210(g) , manufacturers of fire pump engines may use the following test cycle for testing fire pump engines:]

Mode No.Engine speed 1Torque (percent) 2Weighting factors
1Rated1000.30
2Rated750.50
3Rated500.20

1 Engine speed: ±2 percent of point.

2 Torque: NFPA certified nameplate HP for 100 percent point. All points should be ±2 percent of engine percent load value.

40C.F.R. 60 app Table 6 to Subpart IIII of Part 60