40 C.F.R. § 60 app Table 3 to Subpart FFFF of Part 60

Current through October 31, 2024
Appendix Table 3 to Subpart FFFF of Part 60 - Model Rule-Operating Limits for Incinerators and Wet Scrubbers

As stated in § 60.3023 , you must comply with the following:

For these operating parametersYou must establish operating limitsAnd monitoring using these minimum frequencies
Data measurement Data recording Averaging time
1. Charge rateMaximum charge rateContinuousEvery hourDaily for batch units. 3-hour rolling for continuous and intermittent units.a
2. Pressure drop across the wet scrubber or amperage to wet scrubberMinimum pressure drop or amperageContinuousEvery 15 minutes3-hour rolling.a
3. Scrubber liquor flow rateMinimum flow rateContinuousEvery 15 minutes3-hour rolling.a
4. Scrubber liquor pHMinimum pHContinuousEvery 15 minutes3-hour rolling.a

a Calculated each hour as the average of the previous 3 operating hours.

40 C.F.R. 60 app Table 3 to Subpart FFFF of Part 60