40 C.F.R. § 60 app Table 2 to Subpart DDDD of Part 60

Current through November 30, 2024
Appendix Table 2 to Subpart DDDD of Part 60 - Model Rule-Emission Limitations That Apply to Incinerators Before [Date To Be Specified in State Plan] [1]

For the air pollutantYou must meet this
emission limitation2
Using this averaging time3And determining compliance using this method3
Cadmium0.004 milligrams per dry standard cubic meter3-run average (1 hour minimum sample time per run)Performance test (Method 29 of appendix A of this part).
Carbon monoxide157 parts per million by dry volume3-run average (1 hour minimum sample time per run)Performance test (Method 10, 10A, or 10B, of appendix A of this part).
Dioxins/furans (toxic equivalency basis)0.41 nanograms per dry standard cubic meter3-run average (1 hour minimum sample time per run)Performance test (Method 23 of appendix A of this part).
Hydrogen chloride62 parts per million by dry volume3-run average (For Method 26, collect a minimum volume of 120 liters per run. For Method 26A, collect a minimum volume of 1 dry standard cubic meter per run)Performance test (Method 26 or 26A at 40 CFR part 60, appendix A-8).
Lead0.04 milligrams per dry standard cubic meter3-run average (1 hour minimum sample time per run)Performance test (Method 29 of appendix A of this part).
Mercury0.47 milligrams per dry standard cubic meter3-run average (1 hour minimum sample time per run)Performance test (Method 29 or 30B at 40 CFR part 60, appendix A-8) or ASTM D6784-02 (Reapproved 2008).4
Opacity10 percentThree 1-hour blocks consisting of ten 6-minute average opacity valuesPerformance test (Method 9 at 40 CFR part 60, appendix A-4).
Nitrogen oxides388 parts per million by dry volume3-run average (1 hour minimum sample time per run)Performance test (Methods 7 or 7E at 40 CFR part 60, appendix A-4).
Particulate matter70 milligrams per dry standard cubic meter3-run average (1 hour minimum sample time per run)Performance test (Method 5 or 29 of appendix A of this part).
Sulfur dioxide20 parts per million by dry volume3-run average (1 hour minimum sample time per run)Performance test (Method 6 or 6c of appendix A of this part).

1 Applies only to incinerators subject to the CISWI standards through a state plan or the Federal plan prior to June 4, 2010. The date specified in the state plan can be no later than 3 years after the effective date of approval of a revised state plan or February 7, 2018.

2 All emission limitations (except for opacity) are measured at 7 percent oxygen, dry basis at standard conditions.

3 In lieu of performance testing, you may use a CEMS or, for mercury, an integrated sorbent trap monitoring system, to demonstrate initial and continuing compliance with an emissions limit, as long as you comply with the CEMS or integrated sorbent trap monitoring system requirements applicable to the specific pollutant in §§ 60.2710 and 60.2730 . As prescribed in § 60.2710(u) , if you use a CEMS or integrated sorbent trap monitoring system to demonstrate compliance with an emissions limit, your averaging time is a 30-day rolling average of 1-hour arithmetic average emission concentrations.

4 Incorporated by reference, see§ 60.17 .

40 C.F.R. 60 app Table 2 to Subpart DDDD of Part 60

81 FR 41002 , 6/23/2016; 84 FR 15884 , 4/16/2019