Table 149.409-Portable and Semi-Portable Extinguishers, Minimum Quantity and Location
Space | Classification | Minimum quantity and location |
(1) Safety Areas | ||
(i) Communicating corridors | 2-A | One in each main corridor or stairway not more than 150 ft apart. |
(ii) Radio room | 20-B:C | One outside or near each radio room exit. |
(2) Accommodation Spaces | ||
(i) Sleeping quarters | 2-A | One in each sleeping space that fits more than four persons. |
(3) Service Spaces | ||
(i) Galleys | 40-B:C | One for each 2,500 sq ft or fraction thereof, for hazards involved. |
(ii) Storerooms | 2-A | One for each 2,500 sq ft or fraction thereof, located near each exit, either inside or outside the space. |
(iii) Paint room | 40-B | One outside each paint room exit. |
(4) Machinery Spaces | ||
(i) Gas-fired boilers | 40-B:C | Two. |
160-B | One.1 | |
(ii) Oil-fired boilers | 40-B:C | Two. |
160-B | Two.1 | |
(iii) Internal combustion or gas turbine engines | 40-B | One for each engine.2 |
(iv) Open electric motors and generators | 40-B:C | One for each of two motors or generators.3 |
(5) Helicopter Areas | ||
(i) Helicopter landing decks | 160-B | One at each access route. |
(ii) Helicopter fueling facility | 160-B | One at each fuel transfer facility.4 |
1 Not required if a fixed system is installed.
2 If the engine is installed on a weather deck or is open to the atmosphere at all times, one 40-B extinguisher may be used for every three engines.
3 Small electrical appliances, such as fans, are exempt.
4 Not required if a fixed foam system is installed in accordance with 46 CFR 108.489 .
33 C.F.R. §149.409