33 C.F.R. § 127.611

Current through July 31, 2024
Section 127.611 - International shore connection

The marine transfer area for LNG must have an international shore connection that is in accordance with ASTM F1121-87 (Reapproved 2019) (incorporated by reference, see § 127.003 ), a 21/2 inch fire hydrant, and 21/2 inch fire hose of sufficient length to connect the fire hydrant to the international shore connection on the vessel.

33 C.F.R. §127.611

CGD 88-032, 56 FR 35819, July 29, 1991, as amended by CGD 88-049, 60 FR 39796, Aug. 3, 1995; USCG-2000-7223, 65 FR 40057, June 29, 2000; USCG-2019-0444, 87 FR 5691, Feb. 2, 2022
87 FR 5689, 3/4/2022