30 C.F.R. § 250.876

Current through July 31, 2024
Section 250.876 - Fired and exhaust heated components

No later than September 7, 2018, and at least once every 5 years thereafter, you must have qualified third-party inspect, and then you must repair or replace, as needed, the fire tube for tube-type heaters that are equipped with either automatically controlled natural or forced draft burners installed in either atmospheric or pressure vessels that heat hydrocarbons and/or glycol. If inspection indicates tube-type heater deficiencies, you must complete and document repairs or replacements. You must document the inspection results, retain such documentation for at least 5 years, and make the documentation available to BSEE upon request.

30 C.F.R. §250.876

83 FR 49262, Sept. 28, 2018
83 FR 49262, 12/27/2018