Table C-3-Control Door Construction
Location | Minimum required construction |
At least 50 feet from: timbered areas, exposed combustible rock, and any other combustible material1 | Control door that meets the requirements for a ventilation door in conformance with 30 CFR 57.8531 . |
Within 50 feet but no closer than 20 feet of: timbered areas, exposed combustible rock, or other combustible material1 Within 20 feet of: any timbered areas or combustible rock, provided that the timber and combustible rock within the 20 foot distance are coated with one inch of shotcrete, one-half inch of gunite, or other material with equivalent fire protection characteristics and no other combustible material1 is within that distance | Control door that serves as a barrier to the effects of fire and air leakage. The control door shall provide protection at least equivalent to a door constructed of no less than one-quarter inch of plate steel with channel or angle-iron reinforcement to minimize warpage. The framework assembly of the door and the surrounding bulkhead, if any, shall be at least equivalent to the door in fire and air-leakage resistance, and in physical strength. |
Within 20 feet of: timbered areas, exposed combustible rock, or other combustible material1 | Control door that serves as a barrier to fire, the effects of fire, and air-leakage. The door shall provide protection at least equivalent to a door constructed of two layers of wood, each a minimum of three-quarters of an inch in thickness. The wood grain of one layer shall be perpendicular to the wood grain of the other layer. The wood construction shall be covered on all sides and edges with no less than twenty-four gauge sheet steel. The framework assembly of the door and the surrounding bulkhead, if any, shall be at least equivalent to the door in fire and air-leakage resistance, and in physical strength. Roll-down steel doors with a fire-resistance rating of 11/2 hours or greater, but without an insulation core, are acceptable if an automatic sprinkler or deluge system is installed that provides even coverage of the door on both sides. |
1 In this table, "combustible material" does not refer to installed wiring or track support.
30 C.F.R. §57.4760