10 C.F.R. § 434.513

Current through September 30, 2024
Section 434.513 - Occupancy
513.1 Occupancy schedules are default assumptions. The same assumptions shall be made in computing Design Energy Consumption as were used in calculating the Energy Cost Budget.
513.2 Table 513.2.a, Occupancy Density, establishes the density, in ft2 person of conditioned floor area, to be used for each building type. Table 513.2.b, Building Schedule Percentage Multipliers, establishes the percentage of total occupants in the building by hour of the day for each building type.

Table 513.2 . a-Occupancy Density

Building type Conditioned floor area Ft2 person
Assembly50
Office275
Retail300
Warehouse15000
School75
Hotel/Motel250
Restaurant100
Health/Institutional200
Multi-family High-rise Residential2 per unit .1

1 Heat generation: Btu/h per person: 230 Btu/h per person sensible, and 190 Btu/h per person latent. See Tables 512.2 a and b.

View Image

View Image

View Image

View Image

View Image

10 C.F.R. §434.513