Designed to be operated with lamps of the following rated lamp wattage | Tested input voltage[DOUBLE DAGGER][DOUBLE DAGGER] | Minimum standard equation[DOUBLE DAGGER][DOUBLE DAGGER] % |
[GREATER THAN EQUAL TO]50 W and [LESS THAN EQUAL TO]100 W | Tested at 480 V | (1/(1 + 1.24 * P^(-0.351))) - 0.020[DAGGER][DAGGER] |
[GREATER THAN EQUAL TO]50 W and [LESS THAN EQUAL TO]100 W | All others | 1/(1 + 1.24 * P^(-0.351)) |
[GREATER THAN]100 W and [LESS THAN]150[DAGGER] W | Tested at 480 V | (1/(1 + 1.24 * P^(-0.351))) - 0.020 |
[GREATER THAN]100 W and [LESS THAN]150[DAGGER] W | All others | 1/(1 + 1.24 * P^(-0.351)) |
[GREATER THAN EQUAL TO]150 [DOUBLE DAGGER] W and [LESS THAN EQUAL TO]250 W | Tested at 480 V | 0.880 |
[GREATER THAN EQUAL TO]150 [DOUBLE DAGGER] W and [LESS THAN EQUAL TO]250 W | All others | For [GREATER THAN EQUAL TO]150 W and [LESS THAN EQUAL TO]200 W: 0.880 |
For [GREATER THAN]200 W and [LESS THAN EQUAL TO]250 W: 1/(1 + 0.876 * P^(-0.351)) | ||
[GREATER THAN]250 W and [LESS THAN EQUAL TO]500 W | Tested at 480 V | For [GREATER THAN]250 and [LESS THAN]265 W: 0.880 |
For [GREATER THAN EQUAL TO]265 W and [LESS THAN EQUAL TO]500 W: (1/(1 + 0.876 * P^(-0.351)) - 0.010 | ||
[GREATER THAN]250 W and [LESS THAN EQUAL TO]500 W | All others | 1/(1 + 0.876 * P^(-0.351)) |
[GREATER THAN]500 W and [LESS THAN EQUAL TO]1000 W | Tested at 480 V | For [GREATER THAN]500 W and [LESS THAN EQUAL TO]750 W: 0.900 |
For [GREATER THAN]750 W and [LESS THAN EQUAL TO]1000 W: 0.000104 * P + 0.822 | ||
For [GREATER THAN]500 W and [LESS THAN EQUAL TO]1000 W: may not utilize a probe-start ballast | ||
[GREATER THAN]500 W and [LESS THAN EQUAL TO]1000 W | All others | For [GREATER THAN]500 W and [LESS THAN EQUAL TO]750 W: 0.910 |
For [GREATER THAN]750 W and [LESS THAN EQUAL TO]1000 W: 0.000104 * P + 0.832 | ||
For [GREATER THAN]500 W and [LESS THAN EQUAL TO]1000 W: may not utilize a probe-start ballast |
[DAGGER] Includes 150 W fixtures specified in paragraph (b)(3) of this section, that are fixtures rated only for 150 W lamps; rated for use in wet locations, as specified by the NFPA 70 (incorporated by reference, see § 431.323 ), section 410.4(A) ; and containing a ballast that is rated to operate at ambient air temperatures above 50 °C, as specified by UL 1029 (incorporated by reference, see § 431.323 ).
[DOUBLE DAGGER] Excludes 150 W fixtures specified in paragraph (b)(3) of this section, that are fixtures rated only for 150 W lamps; rated for use in wet locations, as specified by the NFPA 70, section 410.4(A) ; and containing a ballast that is rated to operate at ambient air temperatures above 50 °C, as specified by UL 1029.
[DAGGER][DAGGER] P is defined as the rated wattage of the lamp the fixture is designed to operate.
[DOUBLE DAGGER][DOUBLE DAGGER] Tested input voltage is specified in 10 CFR 431.324 .
10 C.F.R. §431.326