Table 1 to Paragraph (b) -Minimum Efficiency Standards for Air-Cooled Commercial Package Air Conditioning and Heating Equipment With a Cooling Capacity Greater Than or Equal to 65,000 Btu/h
[Excluding double-duct air-conditioners and heat pumps]
Cooling capacity | Subcategory | Supplementary heating type | Minimum efficiency 1 | Compliance date: equipment manufactured starting on . . . |
Air-Cooled Commercial Package Air Conditioning and Heating Equipment with a Cooling Capacity Greater Than or Equal to 65,000 Btu/h (Excluding Double-Duct Air Conditioners and Heat Pumps) | ||||
[GREATER THAN EQUAL TO]65,000 Btu/h and <135,000 Btu/h | AC | Electric Resistance Heating or No Heating | IEER = 14.8 | January 1, 2023. |
[GREATER THAN EQUAL TO]65,000 Btu/h and <135,000 Btu/h | AC | All Other Types of Heating | IEER = 14.6 | January 1, 2023. |
[GREATER THAN EQUAL TO]65,000 Btu/h and <135,000 Btu/h | HP | Electric Resistance Heating or No Heating | IEER = 14.1 COP = 3.4 | January 1, 2023. |
[GREATER THAN EQUAL TO]65,000 Btu/h and <135,000 Btu/h | HP | All Other Types of Heating | IEER = 13.9 COP = 3.4 | January 1, 2023. |
[GREATER THAN EQUAL TO]135,000 Btu/h and <240,000 Btu/h | AC | Electric Resistance Heating or No Heating | IEER = 14.2 | January 1, 2023. |
[GREATER THAN EQUAL TO]135,000 Btu/h and <240,000 Btu/h | AC | All Other Types of Heating | IEER = 14.0 | January 1, 2023. |
[GREATER THAN EQUAL TO]135,000 Btu/h and <240,000 Btu/h | HP | Electric Resistance Heating or No Heating | IEER = 13.5 COP = 3.3 | January 1, 2023. |
[GREATER THAN EQUAL TO]135,000 Btu/h and <240,000 Btu/h | HP | All Other Types of Heating | IEER = 13.3 COP = 3.3 | January 1, 2023. |
[GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | AC | Electric Resistance Heating or No Heating | IEER = 13.2 | January 1, 2023. |
[GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | AC | All Other Types of Heating | IEER = 13.0 | January 1, 2023. |
[GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | HP | Electric Resistance Heating or No Heating | IEER = 12.5 COP = 3.2 | January 1, 2023. |
[GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | HP | All Other Types of Heating | IEER = 12.3 COP = 3.2 | January 1, 2023. |
1 See section 3 of appendix A to this subpart for the test conditions upon which the COP standards are based.
Table 2 to Paragraph (b) -Minimum Cooling Efficiency Standards for Water-Cooled Commercial Package Air Conditioning Equipment
Cooling capacity | Supplementary heating type | Minimum efficiency | Compliance date: equipment manufactured starting on . . . |
Water-Cooled Commercial Package Air Conditioning Equipment | |||
<65,000 Btu/h | All | EER = 12.1 | October 29, 2003. |
[GREATER THAN EQUAL TO]65,000 Btu/h and <135,000 Btu/h | No Heating or Electric Resistance Heating | EER = 12.1 | June 1, 2013. |
[GREATER THAN EQUAL TO]65,000 Btu/h and <135,000 Btu/h | All Other Types of Heating | EER = 11.9 | June 1, 2013. |
[GREATER THAN EQUAL TO]135,000 Btu/h and <240,000 Btu/h | No Heating or Electric Resistance Heating | EER = 12.5 | June 1, 2014. |
[GREATER THAN EQUAL TO]135,000 Btu/h and <240,000 Btu/h | All Other Types of Heating | EER = 12.3 | June 1, 2014. |
[GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | No Heating or Electric Resistance Heating | EER = 12.4 | June 1, 2014. |
[GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | All Other Types of Heating | EER = 12.2 | June 1, 2014. |
Table 3 to Paragraph (b) -Minimum Cooling Efficiency Standards for Evaporatively-Cooled Commercial Package Air Conditioning Equipment
Cooling capacity | Supplementary heating type | Minimum efficiency | Compliance date: equipment manufactured starting on . . . |
Evaporatively-Cooled Commercial Package Air Conditioning Equipment | |||
<65,000 Btu/h | All | EER = 12.1 | October 29, 2003. |
[GREATER THAN EQUAL TO]65,000 Btu/h and <135,000 Btu/h | No Heating or Electric Resistance Heating | EER = 12.1 | June 1, 2013. |
[GREATER THAN EQUAL TO]65,000 Btu/h and <135,000 Btu/h | All Other Types of Heating | EER = 11.9 | June 1, 2013. |
[GREATER THAN EQUAL TO]135,000 Btu/h and <240,000 Btu/h | No Heating or Electric Resistance Heating | EER = 12.0 | June 1, 2014. |
[GREATER THAN EQUAL TO]135,000 Btu/h and <240,000 Btu/h | All Other Types of Heating | EER = 11.8 | June 1, 2014. |
[GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | No Heating or Electric Resistance Heating | EER = 11.9 | June 1, 2014. |
[GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | All Other Types of Heating | EER = 11.7 | June 1, 2014. |
Table 4 to Paragraph (b) -Minimum Efficiency Standards for Double-Duct Air Conditioners and Heat Pumps
Cooling capacity | Subcategory | Supplementary heating type | Minimum efficiency 1 | Compliance date: equipment manufactured starting on . . . |
Double-Duct Air Conditioners and Heat Pumps | ||||
[GREATER THAN EQUAL TO]65,000 Btu/h and <135,000 Btu/h | AC | Electric Resistance Heating or No Heating | EER = 11.2 | January 1, 2010. |
[GREATER THAN EQUAL TO]65,000 Btu/h and <135,000 Btu/h | AC | All Other Types of Heating | EER = 11.0 | January 1, 2010. |
[GREATER THAN EQUAL TO]65,000 Btu/h and <135,000 Btu/h | HP | Electric Resistance Heating or No Heating | EER = 11.0 COP = 3.3 | January 1, 2010. |
[GREATER THAN EQUAL TO]65,000 Btu/h and <135,000 Btu/h | HP | All Other Types of Heating | EER = 10.8 COP = 3.3 | January 1, 2010. |
[GREATER THAN EQUAL TO]135,000 Btu/h and <240,000 Btu/h | AC | Electric Resistance Heating or No Heating | EER = 11.0 | January 1, 2010. |
[GREATER THAN EQUAL TO]135,000 Btu/h and <240,000 Btu/h | AC | All Other Types of Heating | EER = 10.8 | January 1, 2010. |
[GREATER THAN EQUAL TO]135,000 Btu/h and <240,000 Btu/h | HP | Electric Resistance Heating or No Heating | EER = 10.6 COP = 3.2 | January 1, 2010. |
[GREATER THAN EQUAL TO]135,000 Btu/h and <240,000 Btu/h | HP | All Other Types of Heating | EER = 10.4 COP = 3.2 | January 1, 2010. |
[GREATER THAN EQUAL TO]240,000 Btu/h and <300,000 Btu/h | AC | Electric Resistance Heating or No Heating | EER = 10.0 | January 1, 2010. |
[GREATER THAN EQUAL TO]240,000 Btu/h and <300,000 Btu/h | AC | All Other Types of Heating | EER = 9.8 | January 1, 2010. |
[GREATER THAN EQUAL TO]240,000 Btu/h and <300,000 Btu/h | HP | Electric Resistance Heating or No Heating | EER = 9.5 COP = 3.2 | January 1, 2010. |
[GREATER THAN EQUAL TO]240,000 Btu/h and <300,000 Btu/h | HP | All Other Types of Heating | EER = 9.3 COP = 3.2 | January 1, 2010. |
1 See section 3 of appendix A to this subpart for the test conditions upon which the COP standards are based.
Table 5 to Paragraph (c) -Minimum Efficiency Standards for Water-Source Heat Pumps (Water-to-Air, Water-Loop)
Cooling capacity | Minimum efficiency | Compliance date: equipment manufactured starting on . . . |
Water-Source Heat Pumps (Water-to-Air, Water-Loop) | ||
<17,000 Btu/h | EER = 12.2 COP = 4.3 | October 9, 2015. |
[GREATER THAN EQUAL TO]17,000 Btu/h and <65,000 Btu/h | EER = 13.0 COP = 4.3 | October 9, 2015. |
[GREATER THAN EQUAL TO]65,000 Btu/h and <135,000 Btu/h | EER = 13.0 COP = 4.3 | October 9, 2015. |
Table 6 to Paragraph (d) -Minimum Efficiency Standards for PTAC and PTHP
Equipment type | Category | Cooling capacity | Efficiency level | Compliance date: products manufactured on and after . . . |
PTAC | Standard Size | <7,000 Btu/h | EER = 11.7 | October 8, 2012.2 |
[GREATER THAN EQUAL TO]7,000 Btu/h and [LESS THAN EQUAL TO]15,000 Btu/h | EER = 13.8-(0.3 * Cap 1 ) | October 8, 2012.2 | ||
>15,000 Btu/h | EER = 9.3 | October 8, 2012.2 | ||
Non-Standard Size | <7,000 Btu/h | EER = 9.4 | October 7, 2010. | |
[GREATER THAN EQUAL TO]7,000 Btu/h and [LESS THAN EQUAL TO]15,000 Btu/h | EER = 10.9-(0.213 * Cap 1 ) | October 7, 2010. | ||
>15,000 Btu/h | EER = 7.7 | October 7, 2010. | ||
PTHP | Standard Size | <7,000 Btu/h | EER = 11.9 COP = 3.3 | October 8, 2012. |
[GREATER THAN EQUAL TO]7,000 Btu/h and [LESS THAN EQUAL TO]15,000 Btu/h | EER = 14.0-(0.3 * Cap 1 ) COP = 3.7-(0.052 * Cap 1 ) | October 8, 2012. | ||
>15,000 Btu/h | EER = 9.5 COP = 2.9 | October 8, 2012. | ||
Non-Standard Size | <7,000 Btu/h | EER = 9.3 COP = 2.7 | October 7, 2010. | |
[GREATER THAN EQUAL TO]7,000 Btu/h and [LESS THAN EQUAL TO]15,000 Btu/h | EER = 10.8-(0.213 * Cap 1 ) COP = 2.9-(0.026 * Cap 1 ) | October 7, 2010. | ||
>15,000 Btu/h | EER = 7.6 COP = 2.5 | October 7, 2010. |
1 "Cap" means cooling capacity in thousand Btu/h at 95 °F outdoor dry-bulb temperature.
2 And manufactured before January 1, 2017. See table 7 to this paragraph (d) for updated efficiency standards that apply to this category of equipment manufactured on and after January 1, 2017.
Table 7 to Paragraph (d) -Updated Minimum Efficiency Standards for PTAC
Equipment type | Category | Cooling capacity | Efficiency level | Compliance date: products manufactured on and after . . . |
PTAC | Standard Size | <7,000 Btu/h | EER = 11.9 | January 1, 2017. |
[GREATER THAN EQUAL TO]7,000 Btu/h and [LESS THAN EQUAL TO]15,000 Btu/h | EER = 14.0-(0.3 * Cap 1 ) | January 1, 2017. | ||
>15,000 Btu/h | EER = 9.5 | January 1, 2017. |
1 "Cap" means cooling capacity in thousand Btu/h at 95 °F outdoor dry-bulb temperature.
Table 8 to Paragraph (e)(1) -Minimum Efficiency Standards for Single Package Vertical Air Conditioners and Single Package Vertical Heat Pumps
Equipment type | Cooling capacity | Sub-category | Efficiency level | Compliance date: products manufactured on and after . . . |
Single package vertical air conditioners and single package vertical heat pumps, single-phase and three-phase | <65,000 Btu/h | AC HP | EER = 9.0 EER = 9.0 COP = 3.0 | January 1, 2010. January 1, 2010. |
Single package vertical air conditioners and single package vertical heat pumps | [GREATER THAN EQUAL TO]65,000 Btu/h and <135,000 Btu/h | AC HP | EER = 8.9 EER = 8.9 COP = 3.0 | January 1, 2010. January 1, 2010. |
Single package vertical air conditioners and single package vertical heat pumps | [GREATER THAN EQUAL TO]135,000 Btu/h and <240,000 Btu/h | AC HP | EER = 8.6 EER = 8.6 COP = 2.9 | January 1, 2010. January 1, 2010. |
Table 9 to Paragraph (e) (2)-Minimum Efficiency Standards for Single Package Vertical Air Conditioners and Single Package Vertical Heat Pumps
Equipment type | Cooling capacity | Sub-category | Efficiency level | Compliance date: products manufactured on and after . . . |
Single package vertical air conditioners and single package vertical heat pumps, single-phase and three-phase | <65,000 Btu/h | AC HP | EER = 9.0 EER = 9.0 COP = 3.0 | January 1, 2010. January 1, 2010. |
Single package vertical air conditioners and single package vertical heat pumps | [GREATER THAN EQUAL TO]65,000 Btu/h and <135,000 Btu/h | AC HP | EER = 10.0 EER = 10.0 COP = 3.0 | October 9, 2015. October 9, 2015. |
Single package vertical air conditioners and single package vertical heat pumps | [GREATER THAN EQUAL TO]135,000 Btu/h and <240,000 Btu/h | AC HP | EER = 10.0 EER = 10.0 COP = 3.0 | October 9, 2016. October 9, 2016. |
Table 10 to Paragraph (e) (3)-Updated Minimum Efficiency Standards for Single Package Vertical Air Conditioners and Single Package Vertical Heat Pumps
Equipment type | Cooling capacity | Sub-category | Efficiency level | Compliance date: products manufactured on and after . . . |
Single package vertical air conditioners and single package vertical heat pumps, single-phase and three-phase | <65,000 Btu/h | AC HP | EER = 11.0 EER = 11.0 COP = 3.3 | September 23, 2019. September 23, 2019. |
Single package vertical air conditioners and single package vertical heat pumps | [GREATER THAN EQUAL TO]65,000 Btu/h and <135,000 Btu/h | AC HP | EER = 10.0 EER = 10.0 COP = 3.0 | October 9, 2015. October 9, 2015. |
Single package vertical air conditioners and single package vertical heat pumps | [GREATER THAN EQUAL TO]135,000 Btu/h and <240,000 Btu/h | AC HP | EER = 10.0 EER = 10.0 COP = 3.0 | October 9, 2016. October 9, 2016. |
Table 11 to Paragraph (f) (1)-Minimum Efficiency Standards for Computer Room Air Conditioners
Equipment type | Net sensible cooling capacity | Minimum SCOP efficiency | |
Downflow | Upflow | ||
Air-Cooled | <65,000 Btu/h | 2.20 | 2.09 |
[GREATER THAN EQUAL TO]65,000 Btu/h and <240,000 Btu/h | 2.10 | 1.99 | |
[GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | 1.90 | 1.79 | |
Water-Cooled | <65,000 Btu/h | 2.60 | 2.49 |
[GREATER THAN EQUAL TO]65,000 Btu/h and <240,000 Btu/h | 2.50 | 2.39 | |
[GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | 2.40 | 2.29 | |
Water-Cooled with Fluid Economizer | <65,000 Btu/h | 2.55 | 2.44 |
[GREATER THAN EQUAL TO]65,000 Btu/h and <240,000 Btu/h | 2.45 | 2.34 | |
[GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | 2.35 | 2.24 | |
Glycol-Cooled | <65,000 Btu/h | 2.50 | 2.39 |
[GREATER THAN EQUAL TO]65,000 Btu/h and <240,000 Btu/h | 2.15 | 2.04 | |
[GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | 2.10 | 1.99 | |
Glycol-Cooled with Fluid Economizer | <65,000 Btu/h | 2.45 | 2.34 |
[GREATER THAN EQUAL TO]65,000 Btu/h and <240,000 Btu/h | 2.10 | 1.99 | |
[GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | 2.05 | 1.94 |
Table 12 to Paragraph (f) (2)-Updated Minimum Efficiency Standards for Floor-Mounted Computer Room Air Conditioners
Equipment type | Downflow and upflow ducted | Upflow non-ducted and horizontal flow | ||||
Net sensible cooling capacity | Minimum NSenCOP efficiency | Net sensible cooling capacity | Minimum NSenCOP efficiency | |||
Downflow | Upflow ducted | Upflow non-ducted | Horizontal flow | |||
Air-Cooled | <80,000 Btu/h | 2.70 | 2.67 | <65,000 Btu/h | 2.16 | 2.65 |
[GREATER THAN EQUAL TO]80,000 Btu/h and <295,000 Btu/h | 2.58 | 2.55 | [GREATER THAN EQUAL TO]65,000 Btu/h and <240,000 Btu/h | 2.04 | 2.55 | |
[GREATER THAN EQUAL TO]295,000 Btu/h and <930,000 Btu/h | 2.36 | 2.33 | [GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | 1.89 | 2.47 | |
Air-Cooled with Fluid Economizer | <80,000 Btu/h | 2.70 | 2.67 | <65,000 Btu/h | 2.09 | 2.65 |
[GREATER THAN EQUAL TO]80,000 Btu/h and <295,000 Btu/h | 2.58 | 2.55 | [GREATER THAN EQUAL TO]65,000 Btu/h and <240,000 Btu/h | 1.99 | 2.55 | |
[GREATER THAN EQUAL TO]295,000 Btu/h and <930,000 Btu/h | 2.36 | 2.33 | [GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | 1.81 | 2.47 | |
Water-Cooled | <80,000 Btu/h | 2.82 | 2.79 | <65,000 Btu/h | 2.43 | 2.79 |
[GREATER THAN EQUAL TO]80,000 Btu/h and <295,000 Btu/h | 2.73 | 2.70 | [GREATER THAN EQUAL TO]65,000 Btu/h and <240,000 Btu/h | 2.32 | 2.68 | |
[GREATER THAN EQUAL TO]295,000 Btu/h and <930,000 Btu/h | 2.67 | 2.64 | [GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | 2.20 | 2.60 | |
Water-Cooled with Fluid Economizer | <80,000 Btu/h | 2.77 | 2.74 | <65,000 Btu/h | 2.35 | 2.71 |
[GREATER THAN EQUAL TO]80,000 Btu/h and <295,000 Btu/h | 2.68 | 2.65 | [GREATER THAN EQUAL TO]65,000 Btu/h and <240,000 Btu/h | 2.24 | 2.60 | |
[GREATER THAN EQUAL TO]295,000 Btu/h and <930,000 Btu/h | 2.61 | 2.58 | [GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | 2.12 | 2.54 | |
Glycol-Cooled | <80,000 Btu/h | 2.56 | 2.53 | <65,000 Btu/h | 2.08 | 2.48 |
[GREATER THAN EQUAL TO]80,000 Btu/h and <295,000 Btu/h | 2.24 | 2.21 | [GREATER THAN EQUAL TO]65,000 Btu/h and <240,000 Btu/h | 1.90 | 2.18 | |
[GREATER THAN EQUAL TO]295,000 Btu/h and <930,000 Btu/h | 2.21 | 2.18 | [GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | 1.81 | 2.18 | |
Glycol-Cooled with Fluid Economizer | <80,000 Btu/h | 2.51 | 2.48 | <65,000 Btu/h | 2.00 | 2.44 |
[GREATER THAN EQUAL TO]80,000 Btu/h and <295,000 Btu/h | 2.19 | 2.16 | [GREATER THAN EQUAL TO]65,000 Btu/h and <240,000 Btu/h | 1.82 | 2.10 | |
[GREATER THAN EQUAL TO]295,000 Btu/h and <930,000 Btu/h | 2.15 | 2.12 | [GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | 1.73 | 2.10 |
Table 13 to Paragraph (f) (2)-Minimum Efficiency Standards for Ceiling-Mounted Computer Room Air Conditioners
Equipment type | Net sensible cooling capacity | Minimum NSenCOP efficiency | |
Ducted | Non-ducted | ||
Air-Cooled with Free Air Discharge Condenser | <29,000 Btu/h | 2.05 | 2.08 |
[GREATER THAN EQUAL TO]29,000 Btu/h and <65,000 Btu/h | 2.02 | 2.05 | |
[GREATER THAN EQUAL TO]65,000 Btu/h and <760,000 Btu/h | 1.92 | 1.94 | |
Air-Cooled with Free Air Discharge Condenser and Fluid Economizer | <29,000 Btu/h | 2.01 | 2.04 |
[GREATER THAN EQUAL TO]29,000 Btu/h and <65,000 Btu/h | 1.97 | 2 | |
[GREATER THAN EQUAL TO]65,000 Btu/h and <760,000 Btu/h | 1.87 | 1.89 | |
Air-Cooled with Ducted Condenser | <29,000 Btu/h | 1.86 | 1.89 |
[GREATER THAN EQUAL TO]29,000 Btu/h and <65,000 Btu/h | 1.83 | 1.86 | |
[GREATER THAN EQUAL TO]65,000 Btu/h and <760,000 Btu/h | 1.73 | 1.75 | |
Air-Cooled with Fluid Economizer and Ducted Condenser | <29,000 Btu/h | 1.82 | 1.85 |
[GREATER THAN EQUAL TO]29,000 Btu/h and <65,000 Btu/h | 1.78 | 1.81 | |
[GREATER THAN EQUAL TO]65,000 Btu/h and <760,000 Btu/h | 1.68 | 1.7 | |
Water-Cooled | <29,000 Btu/h | 2.38 | 2.41 |
[GREATER THAN EQUAL TO]29,000 Btu/h and <65,000 Btu/h | 2.28 | 2.31 | |
[GREATER THAN EQUAL TO]65,000 Btu/h and <760,000 Btu/h | 2.18 | 2.2 | |
Water-Cooled with Fluid Economizer | <29,000 Btu/h | 2.33 | 2.36 |
[GREATER THAN EQUAL TO]29,000 Btu/h and <65,000 Btu/h | 2.23 | 2.26 | |
[GREATER THAN EQUAL TO]65,000 Btu/h and <760,000 Btu/h | 2.13 | 2.16 | |
Glycol-Cooled | <29,000 Btu/h | 1.97 | 2 |
[GREATER THAN EQUAL TO]29,000 Btu/h and <65,000 Btu/h | 1.93 | 1.98 | |
[GREATER THAN EQUAL TO]65,000 Btu/h and <760,000 Btu/h | 1.78 | 1.81 | |
Glycol-Cooled with Fluid Economizer | <29,000 Btu/h | 1.92 | 1.95 |
[GREATER THAN EQUAL TO]29,000 Btu/h and <65,000 Btu/h | 1.88 | 1.93 | |
[GREATER THAN EQUAL TO]65,000 Btu/h and <760,000 Btu/h | 1.73 | 1.76 |
Table 14 to Paragraph (g) (1)-Minimum Efficiency Standards for Variable Refrigerant Flow Multi-Split Air Conditioners and Heat Pumps
Equipment type | Cooling capacity | Heating type 1 | Efficiency level | Compliance date: equipment manufactured on and after . . . |
VRF Multi-Split Air Conditioners (Air-Cooled) | [GREATER THAN EQUAL TO]65,000 Btu/h and <135,000 Btu/h | No Heating or Electric Resistance Heating | 11.2 EER | January 1, 2010. |
All Other Types of Heating | 11.0 EER | January 1, 2010. | ||
[GREATER THAN EQUAL TO]135,000 Btu/h and <240,000 Btu/h | No Heating or Electric Resistance Heating | 11.0 EER | January 1, 2010. | |
All Other Types of Heating | 10.8 EER | January 1, 2010. | ||
[GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | No Heating or Electric Resistance Heating | 10.0 EER | January 1, 2010. | |
All Other Types of Heating | 9.8 EER | January 1, 2010. | ||
VRF Multi-Split Heat Pumps (Air-Cooled) | [GREATER THAN EQUAL TO]65,000 Btu/h and <135,000 Btu/h | No Heating or Electric Resistance Heating | 11.0 EER, 3.3 COP | January 1, 2010. |
All Other Types of Heating | 10.8 EER, 3.3 COP | January 1, 2010. | ||
[GREATER THAN EQUAL TO]135,000 Btu/h and <240,000 Btu/h | No Heating or Electric Resistance Heating | 10.6 EER, 3.2 COP | January 1, 2010. | |
All Other Types of Heating | 10.4 EER, 3.2 COP | January 1, 2010. | ||
[GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | No Heating or Electric Resistance Heating | 9.5 EER, 3.2 COP | January 1, 2010. | |
All Other Types of Heating | 9.3 EER, 3.2 COP | January 1, 2010. | ||
VRF Multi-Split Heat Pumps (Water-Source) | <17,000 Btu/h | Without Heat Recovery | 12.0 EER, 4.2 COP | October 29, 2012. October 29, 2003. |
With Heat Recovery | 11.8 EER, 4.2 COP | October 29, 2012. October 29, 2003. | ||
[GREATER THAN EQUAL TO]17,000 Btu/h and <65,000 Btu/h | All. | 12.0 EER, 4.2 COP | October 29, 2003. | |
[GREATER THAN EQUAL TO]65,000 Btu/h and <135,000 Btu/h | All. | 12.0 EER, 4.2 COP | October 29, 2003. | |
[GREATER THAN EQUAL TO]135,000 Btu/h and <760,000 Btu/h | Without Heat Recovery | 10.0 EER, 3.9 COP | October 29, 2013. | |
With Heat Recovery | 9.8 EER, 3.9 COP | October 29, 2013. |
1 VRF multi-split heat pumps (air-cooled) with heat recovery fall under the category of "All Other Types of Heating" unless they also have electric resistance heating, in which case it falls under the category for "No Heating or Electric Resistance Heating."
Table 15 to Paragraph ( g )(2)-Updated Minimum Efficiency Standards for Variable Refrigerant Flow Multi-Split Air Conditioners and Heat Pumps
Equipment type | Size category | Heating type | Minimum efficiency |
VRF Multi-Split Air Conditioners (Air-Cooled) | [GREATER THAN EQUAL TO]65,000 and <135,000 Btu/h | All | 15.5 IEER. |
[GREATER THAN EQUAL TO]135,000 and <240,000 Btu/h | All | 14.9 IEER. | |
[GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | All | 13.9 IEER. | |
VRF Multi-Split Heat Pumps (Air-Cooled) | [GREATER THAN EQUAL TO]65,000 and <135,000 Btu/h | Heat Pump without Heat Recovery | 14.6 IEER, 3.3 COP. |
Heat Pump with Heat Recovery | 14.4 IEER, 3.3 COP. | ||
[GREATER THAN EQUAL TO]135,000 and <240,000 Btu/h | Heat Pump without Heat Recovery Heat Pump with Heat Recovery | 13.9 IEER, 3.2 COP. 13.7 IEER, 3.2 COP. | |
[GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | Heat Pump without Heat Recovery Heat Pump with Heat Recovery | 12.7 IEER, 3.2 COP. 12.5 IEER, 3.2 COP. | |
VRF Multi-Split Heat Pumps (Water-Source) | <65,000 Btu/h | Heat Pump without Heat Recovery Heat Pump with Heat Recovery | 16.0 IEER, 4.3 COP. 15.8 IEER, 4.3 COP. |
[GREATER THAN EQUAL TO]65,000 and <135,000 Btu/h | Heat Pump without Heat Recovery Heat Pump with Heat Recovery | 16.0 IEER, 4.3 COP. 15.8 IEER, 4.3 COP. | |
[GREATER THAN EQUAL TO]135,000 and <240,000 Btu/h | Heat Pump without Heat Recovery Heat Pump with Heat Recovery | 14.0 IEER, 4.0 COP. 13.8 IEER, 4.0 COP. | |
[GREATER THAN EQUAL TO]240,000 Btu/h and <760,000 Btu/h | Heat Pump without Heat Recovery Heat Pump with Heat Recovery | 12.0 IEER, 3.9 COP. 11.8 IEER, 3.9 COP. |
Table 16 to Paragraph (h)-Minimum Efficiency Standards for Direct Expansion-Dedicated Outdoor Air Systems
Equipment Category | Subcategory | Efficiency level | Compliance date: equipment manufactured starting on . . . |
Direct expansion-dedicated outdoor air systems | (AC)-Air-cooled without ventilation energy recovery systems | ISMRE2 = 3.8 | May 1, 2024. |
(AC w/VERS)-Air-cooled with ventilation energy recovery systems | ISMRE2 = 5.0 | May 1, 2024. | |
(ASHP)-Air-source heat pumps without ventilation energy recovery systems | ISMRE2 = 3.8 ISCOP2 = 2.05 | May 1, 2024. | |
(ASHP w/VERS)-Air-source heat pumps with ventilation energy recovery systems | ISMRE2 = 5.0 ISCOP2 = 3.20 | May 1, 2024. | |
(WC)-Water-cooled without ventilation energy recovery systems | ISMRE2 = 4.7 | May 1, 2024. | |
(WC w/VERS)-Water-cooled with ventilation energy recovery systems | ISMRE2 = 5.1 | May 1, 2024. | |
(WSHP)-Water-source heat pumps without ventilation energy recovery systems | ISMRE2 = 3.8 ISCOP2 = 2.13 | May 1, 2024. | |
(WSHP w/VERS)-Water-source heat pumps with ventilation energy recovery systems | ISMRE2 = 4.6 ISCOP2 = 4.04 | May 1, 2024. |
Table 17 to Paragraph (i)-Minimum Efficiency Standards for Air-Cooled, Three-Phase, Commercial Package Air Conditioning and Heating Equipment With a Cooling Capacity of Less Than 65,000 Btu/h and Air-Cooled, Three-Phase, Small Variable Refrigerant Flow Multi-Split Air Conditioning and Heating Equipment With a Cooling Capacity of Less Than 65,000 Btu/h
Equipment type | Cooling capacity | Subcategory | Minimum efficiency | Compliance date: equipment manufactured starting on . . . |
Commercial Package Air Conditioning Equipment | <65,000 Btu/h | Split-System | 13.0 SEER | June 16, 2008.1 |
Commercial Package Air Conditioning Equipment | <65,000 Btu/h | Single-Package | 14.0 SEER | January 1, 2017.1 |
Commercial Package Air Conditioning and Heating Equipment | <65,000 Btu/h | Split-System | 14.0 SEER 8.2 HSPF | January 1, 2017.1 |
Commercial Package Air Conditioning and Heating Equipment | <65,000 Btu/h | Single-Package | 14.0 SEER 8.0 HSPF | January 1, 2017.1 |
VRF Air Conditioners | <65,000 Btu/h | 13.0 SEER | June 16, 2008.1 | |
VRF Heat Pumps | <65,000 Btu/h | 13.0 SEER 7.7 HSPF | June 16, 2008.1 |
1 And manufactured before January 1, 2025. For equipment manufactured on or after January 1, 2025, see table 18 to this paragraph (i) for updated efficiency standards.
Table 18 to Paragraph ( i )-Updated Minimum Efficiency Standards for Air-Cooled, Three-Phase, Commercial Package Air Conditioning and Heating Equipment With a Cooling Capacity of Less Than 65,000 Btu/h and Air-Cooled, Three-Phase, Small Variable Refrigerant Flow Multi-Split Air Conditioning and Heating Equipment With a Cooling Capacity of Less Than 65,000 Btu/h
Equipment type | Cooling capacity | Subcategory | Minimum efficiency | Compliance date: equipment manufactured starting on. . . |
Commercial Package Air Conditioning Equipment | < 65,000 Btu/h | Split-System | 13.4 SEER2 | January 1, 2025. |
Commercial Package Air Conditioning Equipment | < 65,000 Btu/h | Single-Package | 13.4 SEER2 | January 1, 2025. |
Commercial Package Air Conditioning and Heating Equipment | < 65,000 Btu/h | Split-System | 14.3 SEER2 7.5 HSPF2 | January 1, 2025. |
Commercial Package Air Conditioning and Heating Equipment | < 65,000 Btu/h | Single-Package | 13.4 SEER2 6.7 HSPF2 | January 1, 2025. |
Space-Constrained Commercial Package Air Conditioning Equipment | [LESS THAN EQUAL TO] 30,000 Btu/h | Split-System | 12.7 SEER2 | January 1, 2025. |
Space-Constrained Commercial Package Air Conditioning Equipment | [LESS THAN EQUAL TO] 30,000 Btu/h | Single-Package | 13.9 SEER2 | January 1, 2025. |
Space-Constrained Commercial Package Air Conditioning and Heating Equipment | [LESS THAN EQUAL TO] 30,000 Btu/h | Split-System | 13.9 SEER2 7.0 HSPF2 | January 1, 2025. |
Space-Constrained Commercial Package Air Conditioning and Heating Equipment | [LESS THAN EQUAL TO] 30,000 Btu/h | Single-Package | 13.9 SEER2 6.7 HSPF2 | January 1, 2025. |
Small-Duct, High-Velocity Commercial Package Air Conditioning | < 65,000 Btu/h | Split-System | 13.0 SEER2 | January 1, 2025. |
Small-Duct, High-Velocity Commercial Package Air Conditioning and Heating Equipment | < 65,000 Btu/h | Split-System | 14.0 SEER2 6.9 HSPF2 | January 1, 2025. |
VRF Air Conditioners | < 65,000 Btu/h | 13.4 SEER2 | January 1, 2025. | |
VRF Heat Pumps | < 65,000 Btu/h | 13.4 SEER2 7.5 HSPF2 | January 1, 2025. |
10 C.F.R. §431.97