Section 5569 - Piping, Valves and Fittings(a) The design, fabrication, assembly, test and inspection of the piping system shall be in accordance with Article 146 except that, where dispensing is from a floating structure, suitable lengths of oil-resistant flexible hose may be employed between the shore piping and the piping on the floating structure as made necessary by change in water level or shore line. (1) Piping handling Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), at marine service stations shall be grounded to control stray currents.(2) Piping shall be located so as to be protected from physical damage.(3) A readily accessible valve to shut off the supply from shore shall be provided in each pipeline at or near the approach to the pier and at the shore end of each marine pipeline adjacent to the point where a flexible hose is attached.(4) After completion of the installation, including any paving, that section of the pressure piping system between the pump discharge and the connection for the dispensing facility shall be tested for at least 30 minutes at the maximum operating pressure of the system. Such tests shall be repeated at 5-year intervals thereafter.Cal. Code Regs. Tit. 8, § 5569