Section 5473 - Specific Requirements
(a) The location of a system, as determined by the maximum total contained volume of hydrogen, shall be in the order of preference as indicated by Roman numerals in Table H-1.

Table H-1

Size of Hydrogen System
Nature of LocationLess than 3,000 CF3,000 CF to 15,000 CFIn Excess of 15,000 CF
OutdoorsIII
In a separate buildingIIIIII
In a special roomIIIIIINot Permitted
Inside buildings not in a special room and exposed to other occupanciesIVNot PermittedNot Permitted

(b) The minimum distance in feet from a hydrogen system of indicated capacity located outdoors, in separate buildings or in special rooms to any specified outdoor exposure shall be in accordance with Table H-2.
(c) The distance in Table H-2, Items 1, 14 and 3 to 10 inclusive do not apply where protective structures such as adequate fire walls are located between the system and the exposure.
(d) Hydrogen systems of less than 3,000 CF when located inside buildings and exposed to other occupancies shall be situated in the building so that the system will be as follows:
(1) In an adequately ventilated area as in Section 5475(b).
(2) 20 feet from stored flammable materials or oxidizing gases.
(3) 25 feet from open flames, ordinary electrical equipment or other sources of ignition.
(4) 25 feet from concentrations of people.
(5) 50 feet from intakes of ventilation or air conditioning equipment and air compressors.
(6) 50 feet from other flammable gas storage.
(7) Protected against damage or injury due to falling objects or working activity in the area.
(8) More than one system of 3,000 CF or less may be installed in the same room, provided the systems are separated by at least 50 feet. Each such system shall meet all of the requirements of this Section.

Table H-2

Size of Hydrogen System
Type of Outdoor ExposureLess than 3,000 CF3,000 CF to 15,000 CFIn Excess of 15,000 CF
1.Building orWood Frame Construction*102550
StructureHeavy Timber, Noncombustible or Ordinary Construction*01025*
Fire Resistive Construction*000
2.Wall OpeningsNot above any part of a system101010
Above any part of a system252525
3.Flammable liquids0-1,000 gallons102525
above groundIn excess of 1,000 gallons255050
4.Flammable liquidsTank101010
below ground--
0-1,000 gallonsVent or fill opening of tank252525
5.Flammable liquidsTank202020
below ground--
in excess of 1,000 gallonsVent or fill opening of tank252525
6.Flammable gas storage0-15,000 CF capacity102525
age, either high
pressure or low pressurein excess of 15,000 CF capacity255050
7.Oxygen Storage12,000 CF or lessRefer to NFPA No. 51, Gas Systems for Welding and Cutting
More than 12,000 CFRefer to NFPA No. 50, Bulk Oxygen Systems at Consumer Sites
8.Fast burning solids such as ordinary lumber, excelsior or paper505050
9.Slow burning solids such as heavy timber or coal252525
10.Open flames and other sources of ignition252525
11.Air compressor intakes or inlets to ventilating or air-conditioning equipment505050
12.Concentration of people***255050
13.Public Sidewalks151515
14.Line of adjoining property which may be built upon555

* Refer to NFPA No. 220, Standard Types of Building Construction for definitions of various types of construction.

** But not less than one-half the height of adjacent side wall of the structure.

*** In congested areas such as offices, lunchrooms, locker rooms, time-clock areas and places of public assembly.

Cal. Code Regs. Tit. 8, § 5473