Cal. Code Regs. tit. 8 § 4657

Current through Register 2024 Notice Reg. No. 44, November 1, 2024
Section 4657 - General
(a) Compressed gas cylinders, portable tanks, and cargo tanks shall have pressure relief devices installed and maintained in accordance with Compressed Gas Association Pamphlets S-1.1-1963 and 1965 addenda and S-1.2-1963. Types of safety relief devices as covered by this section are designated as follows:
(1) Type CG-1: Frangible disc.
(2) Type CG-2; Fusible plug or reinforced fusible plug utilizing a fusible alloy with yield temperature not over 170° F, nor less than 157° F (165° F nominal).
(3) Type CG-3; Fusible plug or reinforced fusible plug utilizing a fusible alloy with yield temperature not over 220° F, nor less than 208° F (212° F nominal).
(4) Type CG-4: Combination frangible disc-fusible plug, utilizing a fusible alloy with yield temperature not over 170°F, nor less than 157° F (165° F nominal)
(5) Type CG-5: Combination frangible disc-fusible plug, utilizing a fusible alloy with yield temperature not over 220° F nor less than 208° F (212° F nominal).
(6) Type CG-7: Safety relief valve.
(7) Type CG-8: Combination safety relief valve and fusible plug.
(b) All safety relief devices covered by this section shall meet the design, construction, marking and test specification of the "Compressed Gas Association Safety Relief Device Standards Part I--Cylinders for Compressed Gases: S 1.1-1963."

Cal. Code Regs. Tit. 8, § 4657

1. Amendment of subsection (a) filed 11-18-76; effective thirtieth day thereafter (Register 76, No. 47).
2. Editorial correction of subsection (a)(4) (Register 97, No. 23).