Automatic Fire Protection* Provided | Fire Resistance | Maximum Floor Area | Total Allowable Quantities Gals./sq. ft./floor area |
yes | 2-hour | 500 sq. ft. | 10 |
no | 2-hour | 500 sq. ft. | 4 |
yes | 1-hour | 150 sq. ft. | 5 |
no | 1-hour | 150 sq. ft. | 2 |
* Fire protection system shall be sprinkler, water spray, carbon dioxide, or other system approved by a nationally recognized testing laboratory for this purpose.
Every inside storage room shall be provided with either a gravity or a mechanical exhausting system. Such system shall commence not more than 12 inches above the floor and be designed to provide for a complete change of air within the room at least 6 times per hour. If a mechanical exhausting system is used, it shall be controlled by a switch located outside of the door. The ventilating equipment and any lighting fixtures shall be operated by the same switch. An electric pilot light shall be installed adjacent to the switch if Category 1, 2 or 3 flammable liquids are dispensed within the room. Where gravity ventilation is provided, the fresh air intake, as well as the exhausting outlet from the room, shall be on the exterior of the building in which the room is located.
Cal. Code Regs. Tit. 8, § 1931
2. Editorial correction of subsection (e) (Register 95, No. 21).
3. Amendment of section heading and section filed 5-5-2014; operative 5-6-2014 pursuant to Government Code section 11343.4(b)(3) (Register 2014, No. 19).
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.
2. Editorial correction of subsection (e) (Register 95, No. 21).
3. Amendment of section heading and section filed 5-5-2014; operative 5-6-2014 pursuant to Government Code section 11343.4(b)(3) (Register 2014, No. 19).