For the purpose of this Order 530 (d), the electrical equipment installed in out-of-doors installations for stationary storage or the transfer of natural gas shall be suitable for use in a Class 1, Division 1, Group D hazardous location when installed within 10 feet in any direction of any connection used for the transfer of natural gas.
In order to comply with the "source of ignition" provisions of Order 531 (a) electrical switches, lamps, etc., located outside the above 10-foot area, but within the area specified in Order 531 (a) shall be suitable for use in a Class 1, Division 2, Group D, hazardous location. All electrical motors within this area shall be suitable for use in out-of-doors locations and shall be either:
Cal. Code Regs. Tit. 8, § 530