Compressed gases shall not be used for pressure testing of any object until a safe pressure and procedure have been established.
Except where pressure tested in accordance with (d), elastic materials must not be gas tested at pressures above 67% of the minimum specified yield point at test temperature. Brittle materials must not be gas tested above 40% of the minimum specified ultimate strength without remote operation and missile shielding. "Brittle Material" is defined for this section as having a minimum specified elongation of 4% or less.
Threaded connections shall conform to the following table:
MINIMUM NUMBER OF THREADS PER CONNECTION | ||||||||
(a) Pressures up to and including 300 psi | ||||||||
Size of pipe connection, in.......................... | 1 & 1 1/4 | 1 1/2 & 2 | 2 1/2 to 4 | 4 1/2 to 6 | 7 & 8 | 9 & 10 | 12 | |
Threads engaged.......................... | 4 | 5 | 7 | 8 | 10 | 12 | 13 | |
Min. plate thickness required, in.......................... | 0.348 | 0.435 | 0.875 | 1.0 | 1.25 | 1.5 | 1.625 | |
(b) Pressures above 300 psi | ||||||||
Size of pipe connection, in.......................... | 1/2 & 3/4 | 1 to 1 1/2 | 2 | 2 1/2 to 3 | 4 to 6 | 10 | 12 | |
Threads engaged.......................... | 6 | 7 | 8 | 8 | 10 | 13 | 14 | |
Min. plate thickness required, in.......................... | 0.43 | 0.61 | 0.70 | 1.0 | 1.25 | 1.62 | 1.75 |
Such instructions may include applicable data and recommendations furnished by the plug manufacturer and must include the following as a minimum:
The requirement for a relief valve may be waived by a Qualified Pressure Vessel Safety Engineer or Certified Pressure Vessel Inspector if the only source of test pressure is a handpump.
See Petroleum Safety Orders, Sections 6879, 6880 and 6881 for requirements covering transfer operations at sidings inside petroleum refineries and distribution plants.
The Qualified Transfer Attendant shall be instructed in all phases of the transfer operation. The instructions shall include a prohibition against overfilling any tank. Note: All valves in the transfer system must be fully open in order for an excess flow valve to function, so internal valves or check valves should be used whenever possible. The tank car excess flow valves are located in the internal piping beneath the dome.
NOTE: Bonding and grounding of the tankcar and transfer equipment may be required for compressed flammable gases by railroad leasing agreement or by the local fire official.
Valves on vehicles must be closed and locked except during transfer. Where vehicular container valves cannot be locked closed, the filling hose(s) must be disconnected when the qualified attendant is not present.
Personal protective devices and safety equipment which are required and used for stationary storage facilities must be provided. Fire extinguishers must be provided for flammable compressed gases and anhydrous ammonia as required by the applicable safety order.
Cal. Code Regs. Tit. 8, § 560