Current through Register 2024 Notice Reg. No. 50, December 13, 2024
Section 1150 - Park Electrical Disconnecting Means(a) Each service equipment enclosure for the park shall be provided with a single main disconnect switch or circuit breaker lockable in the open position for disconnecting the electrical wiring system or systems of the park.(b) A disconnecting means shall be provided for disconnecting each distribution transformer. When the disconnecting means is not installed immediately adjacent to the distribution transformer, it shall be identified as to its usage and shall be arranged to be locked in the open position.Cal. Code Regs. Tit. 25, § 1150
1. Amendment of section heading and section filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28). Note: Authority cited: Section 18300, Health and Safety Code. Reference: Section 18670, Health and Safety Code.
1. Amendment of section heading and section filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).