Cal. Code Regs. tit. 25 § 862

Current through Register 2024 Notice Reg. No. 50, December 13, 2024
Section 862 - Vertical Clearances

The minimum vertical clearance to be maintained for open electrical conductors are as follows:

(a) Above roofs--eight feet (2.4 meters).
(b) Above walkways and at attachment point of buildings--10 feet (3.0 meters).
(c) Above driveways and parking areas--15 feet (4.5 meters).

Cal. Code Regs. Tit. 25, § 862