Current through Register 2024 Notice Reg. No. 50, December 13, 2024
Section 806 - Location of Liquefied Petroleum Gas Tanks(a) No tank or cylinder shall be maintained within an enclosed housing accommodation, nor within five (5) feet (1.5 meters) of a source of ignition, nor with the outlet less than five (5) feet (1.5 meters) away from any building opening which is below the level of such outlet.(b) No tank or cylinder shall be maintained or stored beneath any shed, structure, mobile home, recreational vehicle, commercial coach, or other housing accommodation in a labor camp.(c) Tanks shall be maintained to be separated from the nearest building, structure, mobile home, recreational vehicle, commercial coach or other housing accommodations with a minimum clearance of ten (10) feet (3 meters) for tanks with a capacity of 61 to 576 gallons (230.5 to 2177.2 liters) and twenty-five (25) feet (7.5 meters) minimum clearance for tanks with a capacity of 576 to 2000 gallons (2177.2 to 7560 liters).Cal. Code Regs. Tit. 25, § 806
1. Editorial correction filed 11-18-82 (Register 82, No. 47). Note: Authority cited: Sections 17003.5 and 17040, Health and Safety Code. Reference: Section 17040, Health and Safety Code.
1. Editorial correction filed 11-18-82 (Register 82, No. 47).