Cal. Code Regs. tit. 23 § 2637.2

Current through Register 2024 Notice Reg. No. 43, October 25, 2024
Section 2637.2 - Overfill Prevention Equipment Inspection
(a) Owners or operators of underground storage tanks that do not meet section 2635(c)(2) shall meet one the following:
(1) Underground storage tanks installed before October 1, 2018 shall have the overfill prevention equipment inspected at all of the following times:
(A) Once by October 13, 2018 and every 36 months thereafter; and
(B) Within 30 days of the date of the completion of a repair.
(2) Underground storage tanks installed on or after October 1, 2018 shall have the overfill prevention equipment inspected at all of the following times:
(A) Upon the completion of an installation and every 36 months thereafter; and
(B) Within 30 days of the date of the completion of a repair.
(b) Overfill prevention equipment inspections shall be conducted using an inspection procedure that demonstrates that the overfill prevention equipment is set to activate at the correct level specified in section 2635(c)(1) and will activate when regulated stored substance reaches that level. These inspections shall be performed in accordance with manufacturer's guidelines or standards. If there are no manufacturer's guidelines or standards, the overfill prevention equipment shall be inspected using an applicable method specified in an industry code or engineering standard. If there are no applicable manufacturer's guidelines, industry codes, or engineering standards, an inspection method approved by a state registered professional engineer shall be used.
(c) Overfill prevention equipment inspections shall be performed by a service technician meeting the requirements of section 2715(f).
(d) The results of the overfill prevention equipment inspection shall be recorded on the "Overfill Prevention Equipment Inspection Report Form" located in Appendix IX.
(e) Owners or operators shall submit a copy of the "Overfill Prevention Equipment Inspection Report Form" to the local agency within 30 days of the completion of the overfill prevention equipment inspection.
(f) Owners or operators shall notify the local agency at least 48 hours prior to conducting the inspection.

Cal. Code Regs. Tit. 23, § 2637.2

1. New section filed 8-27-2018; operative 10-1-2018 (Register 2018, No. 35).

Note: Authority cited: Sections 25299.3 and 25299.7, Health and Safety Code. Reference: Sections 25281, 25284.1, 25289 and 25292.1, Health and Safety Code; and 40 CFR §§ 280.20, 280.33 and 280.35.

1. New section filed 8-27-2018; operative 10/1/2018 (Register 2018, No. 35).