Cal. Code Regs. tit. 22 § 66265.191

Current through Register 2024 Notice Reg. No. 49, December 6, 2024
Section 66265.191 - Assessment of Existing Tank System's Integrity
(a) For each existing tank system that does not have secondary containment meeting the requirements of section 66265.193, the owner or operator shall determine that the tank system is not leaking or is unfit for use. Except as provided in subsections (c) and (e) of this section, the owner or operator shall obtain and keep on file at the facility a written assessment reviewed and certified by an independent, qualified, professional engineer, registered in California, in accordance with section 66270.11(d), that attests to the tank system's integrity.
(b) This assessment shall determine that the tank system is adequately designed and has sufficient structural strength and compatibility with the waste(s) to be transferred, stored or treated to ensure that it will not collapse, rupture, or fail. At a minimum, this assessment shall consider the following:
(1) design standard(s), if available, according to which the tank and ancillary equipment were constructed;
(2) hazardous characteristics of the waste(s) that have been or will be handled;
(3) existing corrosion protection measures;
(4) documented age of the tank system, if available, (otherwise, an estimate of the age); and
(5) results of a leak test, internal inspection, or other tank integrity examination such that:
(A) for non-enterable underground tanks, this assessment shall consist of a leak test that is capable of taking into account the effects of temperature variations, tank end deflection, vapor pockets, and high water table effects,
(B) for other than non-enterable underground tanks and for ancillary equipment, this assessment shall be either a leak test, as described above, or an internal inspection and/or other tank integrity examination certified by an independent, qualified, professional engineer, registered in California, in accordance with section 66270.11(d) that addresses cracks, leaks, corrosion, and erosion.
(c) For tank systems that transfer, store or treat materials that become hazardous wastes this assessment shall be conducted within 12 months after the date that the waste becomes a hazardous waste, except as provided in subsection (g) of this section.
(d) If, as a result of the assessment conducted in accordance with subsection (a) or (e) of this section, a tank system is found to be leaking or unfit for use, the owner or operator shall comply with the requirements of section 66265.196.
(e)
(1) Notwithstanding subsections (a) through (c) of this section, for each existing tank system that does not have secondary containment meeting the requirements of section 66265.193 and which meets the criteria specified in subsection (e)(2) of this section, the assessment specified in subsection (g) of this section shall be conducted by January 24, 1998. This assessment shall be reviewed and certified by an independent, qualified, professional engineer, registered in California, in accordance with section 66270.11(d), that attests to the tank system's integrity. The assessment shall be kept on file at the facility until closure of the facility and shall be valid for a period of one year from the date the assessment was certified.
(2) The provisions of subsection (e)(1) of this section apply only to:
(A) onground or aboveground tank systems containing only non-RCRA hazardous wastes generated onsite, and tank systems authorized under Permit-by-Rule pursuant to Chapter 45 of this division, Conditional Authorization pursuant to HSC 25200.3, and Conditional Exemption pursuant to HSC 25201.5, and
(B) onground or aboveground tank systems containing RCRA hazardous wastes generated onsite, if:
1. the owner or operator is a very small quantity generator as defined in section 66260.10 of this division, or a small quantity generator as defined in section 66260.10 of this division, or
2. the owner or operator is not subject to regulation in 40 CFR part 265 pursuant to an exemption in 40 CFR section 265.1, but the owner or operator is subject to the standards of this article.
(f) A generator or owner or operator authorized pursuant to Permit-by-Rule pursuant to Chapter 45 of this division, Conditional Authorization pursuant to HSC 25200.3, or Conditional Exemption pursuant to HSC 25201.5, operating a non-RCRA underground tank system or an underground tank system otherwise exempt from permitting requirements pursuant to the federal act, shall comply with the applicable standards of Title 23 of the California Code of Regulations relating to underground tank systems.
(g) The tank system assessment shall include all of the following information:
(1) tank configuration (i.e., horizontal, vertical), and gross capacity (in gallons);
(2) design standard(s), if available, according to which the tank and ancillary equipment were constructed and all of the following information;
(A) material of construction;
(B) material thickness and the method used to determine the thickness;
(C) description of tank system piping (material, diameter);
(D) description of any internal and external pumps; and
(E) sketch or drawing of tank including dimensions.
(3) documented age of the tank system, if available, otherwise, an estimate of the age based on owner or operator knowledge;
(4) description and evaluation of the adequacy of any leak detection equipment;
(5) description and evaluation of any corrosion protection equipment;
(6) description and evaluation of any spill prevention or overfill equipment;
(7) hazardous characteristics of the waste(s) that have been or will be handled;
(8) description of any structural damage or inadequate construction or installation such as cracks, punctures, or damaged fittings. All discrepancies shall be documented in the assessment and remedied before the tank system is certified for use.
(9) results of a leak test, internal inspection, or other tank system integrity examination including the type of integrity examination performed (i.e., ultrasonic, internal examination, volumetric tank test, pipeline pressure test). Tank system integrity or leak test requirements must be in compliance with all local requirements. Prior to conducting a tank system integrity test or leak test, contact local agency staff for local requirements.
(10) estimated remaining service life of the tank system based on findings of subsections (g)(1) through (g)(9).

Cal. Code Regs. Tit. 22, § 66265.191

Note: Authority cited: Sections 25150, 25159 and 58012, Health and Safety Code. Reference: Sections 25159 and 25159.5, Health and Safety Code; and 40 CFR Section 265.191.

Note: Authority cited: Sections 25150, 25159 and 58012, Health and Safety Code. Reference: Sections 25159 and 25159.5, Health and Safety Code; 40 CFR Section 265.191.

1. New section filed 5-24-91; operative 7-1-91 (Register 91, No. 22).
2. Amendment filed 6-19-95 as an emergency; operative 6-19-95 (Register 95, No. 25). A Certificate of Complaince must be transmitted to OAL by 10-17-95 or emergency language will be repealed by operation of law on the following day.
3. Amendment refiled 10-16-95 as an emergency; operative 10-16-95 (Register 95, No. 42). A Certificate of Compliance must be transmitted to OAL by 2-13-96 or emergency language will be repealed by operation of law on the following day.
4. Amendment refiled 2-16-96 as an emergency; operative 2-16-96 (Register 96, No. 7). A Certificate of Compliance must be transmitted to OAL by 6-15-96 or emergency language will be repealed by operation of law on the following day.
5. Amendment refiled 6-17-96 as an emergency; operative 6-17-96 (Register 96, No. 25). A Certificate of Compliance must be transmitted to OAL by 10-15-96 or emergency language will be repealed by operation of law on the following day.
6. Amendment refiled 10-15-96 as an emergency; operative 10-15-96 (Register 96, No. 42). A Certificate of Compliance must be transmitted to OAL by 2-12-97 or emergency language will be repealed by operation of law on the following day.
7. Amendment refiled 2-11-97 as an emergency, including amendment of Note; operative 2-11-97 (Register 97, No. 7). A Certificate of Compliance must be transmitted to OAL by 6-11-97 or emergency language will be repealed by operation of law on the following day.
8. Certificate of Compliance as to 2-11-97 order transmitted to OAL 6-10-97; disapproved by OAL and order of repeal as to 2-11-97 filed on 7-24-97 (Register 97, No. 30).
9. Certificate of Compliance as to 2-11-97 order, including amendment of section and Note, resubmitted to OAL and approved on 7-24-97 (Register 97, No. 30).
10. Change without regulatory effect amending subsection (g)(3) filed 7-1-2004 pursuant to section 100, title 1, California Code of Regulations (Register 2004, No. 27).
11. Amendment of subsection (a), repealer of subsections (a)(1)-(a)(2)(B)2., amendment of subsection (c), repealer of subsections (c)(1)-(c)(2)(B)2. and amendment of Note filed 9-8-2006; operative 10-8-2006 (Register 2006, No. 36).
12. Amendment of subsection (e)(2)(B)1. filed 5-6-2024; operative 7/1/2024 (Register 2024, No. 19).