Current through Register 2024 Notice Reg. No. 45, November 8, 2024
Section 66264.1032 - Standards: Process Vents(a) The owner or operator of a facility with process vents associated with distillation, fractionation, thin-film evaporation, solvent extraction, or air or steam stripping operations managing hazardous wastes organic concentrations of at least 10 ppmw shall either:(1) reduce total organic emissions from all affected process vents at the facility below 1.4 kg/h (3 lb/h) and 2.8 Mg/yr (3.1 tons/yr); or(2) reduce, by use of a control device, total organic emissions from all affected process vents at the facility by 95 weight percent.(b) If the owner or operator installs a closed-vent system and control device to comply with the provisions of subsection (a) of this section the closed-vent system and control device shall meet the requirements of Section 66264.1033.(c) Determinations of vent emissions and emission reduction or total organic compound concentrations achieved by add-on control devices shall be based on engineering calculations or performance tests. If performance tests are used to determine vent emissions, emission reductions, or total organic compound concentrations achieved by add-on control devices, the performance tests shall conform with the requirements of Section 66264.1034(c).(d) When an owner or operator and the Department do not agree on determinations of vent emissions and/or emission reductions or total organic compound concentrations achieved by add-on control devices based on engineering calculations, the procedures in Section 66264.1034(c) shall be used to resolve the disagreement.Cal. Code Regs. Tit. 22, § 66264.1032
1. New section filed 12-23-92; operative 1-22-93 (Register 93, No. 2). Note: Authority cited: Sections 25150 and 25159, Health and Safety Code. Reference: Sections 25159 and 25159.5, Health and Safety Code; 40 CFR section 264.1032.
1. New section filed 12-23-92; operative 1-22-93 (Register 93, No. 2).