(a) The distribution system for each community and nontransient-noncommunity water system shall be classified pursuant to Table 64413.3-A unless modified pursuant to subsection (b). For a wholesaler, the population served shall include the customers served by its retailers. Table 64413.3-A. Distribution System Classifications
| Population Served | Class |
| 1,000 or less | D1 |
| 1,001 through 10,000 | D2 |
| 10,001 through 50,000 | D3 |
| 50,001 through 5 million | D4 |
| Greater than 5 million | D5 |
(b) The class determined pursuant to (a) shall be upgraded by one level if the population served is 5 million or less and the sum of all the points from paragraphs (1) through (6) exceeds 20. (1) The points for pressure zones shall be zero for up to three zones, 4 for four to ten zones, or 6 for more than ten zones.(2) The points for disinfectants used shall be zero if no disinfectant is applied in the distribution system and no more than one type of disinfectant residual is entering the distribution system. The points shall be 5 if a single disinfectant or ammonia is applied in the distribution system. The points shall be 8 if there are multiple disinfectants in the system.(3) The points based on the largest single pump in the system for which the distribution operator is responsible shall be 4 for up to fifty horsepower, or 6 for fifty or more horsepower.(4) The points for distribution storage reservoirs in the system shall be 4 for one to five reservoirs, or 6 for greater than five.(5) The points for one or more existing uncovered distribution reservoirs shall be 10.(6) The points to be added if any of the distribution system customers are also served by a non-potable water distribution system shall be 6. This does not apply to wholesalers if the only customers receiving non-potable water are served by its retailers.Cal. Code Regs. Tit. 22, § 64413.3
1. New section filed 12-26-2000 as an emergency; operative 1-1-2001 (Register 2000, No. 52). A Certificate of Compliance must be transmitted to OAL by 5-1-2001 or emergency language will be repealed by operation of law on the following day.
2. New section refiled 4-25-2001 as an emergency; operative 5-2-2001 (Register 2001, No. 17). A Certificate of Compliance must be transmitted to OAL by 8-30-2001 or emergency language will be repealed by operation of law on the following day.
3. Certificate of Compliance as to 4-25-2001 order transmitted to OAL 7-12-2001 and filed 8-13-2001 (Register 2001, No. 33). Note: Authority cited: Sections 100275 and 106910, Health and Safety Code. Reference: Sections 106875, 106910 and 116555, Health and Safety Code.
1. New section filed 12-26-2000 as an emergency; operative 1-1-2001 (Register 2000, No. 52). A Certificate of Compliance must be transmitted to OAL by 5-1-2001 or emergency language will be repealed by operation of law on the following day.
2. New section refiled 4-25-2001 as an emergency; operative 5-2-2001 (Register 2001, No. 17). A Certificate of Compliance must be transmitted to OAL by 8-30-2001 or emergency language will be repealed by operation of law on the following day.
3. Certificate of Compliance as to 4-25-2001 order transmitted to OAL 7-12-2001 and filed 8-13-2001 (Register 2001, No. 33).