Cal. Code Regs. tit. 19 § 578.5

Current through Register 2024 Notice Reg. No. 50, December 13, 2024
Section 578.5 - Precautionary Pressurization Measures
(a) A rechargeable stored pressure type extinguisher shall be pressurized only to the charging pressure specified on the extinguisher nameplate. A regulated source of pressure, set no higher than 25 psi (172 kPa) above the operating (service) pressure, shall be used to pressurize fire extinguishers. An unregulated source of pressure, such as a nitrogen cylinder without a pressure regulator, shall never be used because the fire extinguisher could be over-pressurized and possibly rupture. A fire extinguisher shall never be left connected to the regulator of a high-pressure source for an extended period of time. A defective regulator could cause the container to rupture due to excess pressure.
(b) The gauge used to set the regulated source of pressure shall be calibrated at least annually.

Cal. Code Regs. Tit. 19, § 578.5