Section 575.15 - Conductivity Test(a) An annual conductivity test shall be conducted on all carbon dioxide hose assemblies. Hose assemblies found to be nonconductive shall be replaced.(b) Carbon dioxide hose assemblies that pass a conductivity test shall have the test information recorded on a suitable metallic label or equally durable material that has a minimum size of 1/2 in. x 3 in. (1.3 cm x 7.6 cm). The label shall be affixed to the hose by means of a heatless process. The label shall include the following information: (1) Month and year the test was performed, indicated by perforation, such as is done by a hand punch.(2) Initials and EE# of person performing the test.Cal. Code Regs. Tit. 19, § 575.15
1. New section filed 12-27-2001; operative 1-1-2002 pursuant to Government Code section 11343.4 (Register 2001, No. 52). Note: Authority cited: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.