Current through Register 2024 Notice Reg. No. 50, December 13, 2024
Section 1918.70 - Electrical Requirements(a) General. All electrical equipment and wiring shall comply with the requirements set forth in Part 3, Title 24, California Administrative Code.(b) Emergency Pump Cut-Off. All electrically energized vapor collection equipment shall be directly connected to, and controlled by, an emergency pump cut-off switch.(c) Cut-Off Switch Location. The emergency pump cut-off switch shall be located in a readily accessible and clearly visible location, outside of any enclosure, within 75 feet of but no closer than 15 feet to any gasoline dispenser.(d) Labeling. The emergency pump cut-off switch shall be clearly and legibly labeled as to its function.Cal. Code Regs. Tit. 19, § 1918.70
1. Amendment filed 9-27-85; effective thirtieth day thereafter (Register 85, No. 41). Note: Authority cited: Section 41956, Health and Safety Code. Reference: Sections 41956 and 41958, Health and Safety Code.
1. Amendment filed 9-27-85; effective thirtieth day thereafter (Register 85, No. 41).