Section 1918.70 - Electrical Requirements
(a) General. All electrical equipment and wiring shall comply with the requirements set forth in Part 3, Title 24, California Administrative Code.
(b) Emergency Pump Cut-Off. All electrically energized vapor collection equipment shall be directly connected to, and controlled by, an emergency pump cut-off switch.
(c) Cut-Off Switch Location. The emergency pump cut-off switch shall be located in a readily accessible and clearly visible location, outside of any enclosure, within 75 feet of but no closer than 15 feet to any gasoline dispenser.
(d) Labeling. The emergency pump cut-off switch shall be clearly and legibly labeled as to its function.