Cal. Code Regs. tit. 17 § 95469

Current through Register 2024 Notice Reg. No. 36, September 6, 2024
Section 95469 - Monitoring Requirements
(a)Surface Emissions Monitoring Requirements: Any owner or operator of a MSW landfill with a gas collection and control system must conduct instantaneous and integrated surface monitoring of the landfill surface quarterly using the procedures specified in section 95471(c).
(1)Instantaneous Surface Monitoring: Any reading exceeding the limit specified in section 95465(a)(1) must be recorded as an exceedance and the following actions must be taken:
(A) The owner or operator must record the date, location, and value of each exceedance, along with re-test dates and results. The location of each exceedance must be clearly marked and identified on a topographic map of the MSW landfill, drawn to scale with the location of both the grids and the gas collection system clearly identified.
(B) Corrective action must be taken by the owner or operator such as, but not limited to, cover maintenance or repair, or well vacuum adjustments and the location must be remonitored within ten calendar days of a measured exceedance.
1. If the re-monitoring of the location shows a second exceedance, additional corrective action must be taken and the location must be re-monitored again no later than 10 calendar days after the second exceedance.
2. If the re-monitoring shows a third exceedance, the owner or owner or operator must install a new or replacement well as determined to achieve compliance no later than 120 calendar days after detecting the third exceedance, or it is a violation of this subarticle.
(C) Any closed or inactive MSW landfill, or any closed or inactive areas on an active MSW landfill that has no monitored exceedances of the limit specified in section 95465(a)(1) after four consecutive quarterly monitoring periods may monitor annually. Any exceedances of the limit specified in section 95465(a)(1) detected during the annual monitoring that can not be remediated within 10 calendar days will result in a return to quarterly monitoring of the landfill.
(D) Any exceedances of the limit specified in section 95465(a)(1) detected during any compliance inspections will result in a return to quarterly monitoring of the landfill.
(2)Integrated Surface Monitoring: Any reading exceeding the limit specified in section 95465(a)(2) must be recorded as an exceedance and the following actions must be taken:
(A) The owner or operator must record the average surface concentration measured as methane for each grid along with re-test dates and results. The location of the grids and the gas collection system must be clearly marked and identified on a topographic map of the MSW landfill drawn to scale.
(B) Within 10 calendar days of a measured exceedance, corrective action must be taken by the owner or operator such as, but not limited to, cover maintenance or repair, or well vacuum adjustments and the grid must be re-monitored.
1. If the re-monitoring of the grid shows a second exceedance, additional corrective action must be taken and the location must be re-monitored again no later than 10 calendar days after the second exceedance.
2. If the re-monitoring in section 95469(a)(2)(B)1. shows a third exceedance, the owner or operator must install a new or replacement well as determined to achieve compliance no later than 120 calendar days after detecting the third exceedance, or it is a violation of this subarticle.
(C) Any closed or inactive MSW landfill, or any closed or inactive areas on an active MSW landfill that has no monitored exceedances of the limit specified in section 95465(a)(2) after 4 consecutive quarterly monitoring periods may monitor annually. Any exceedances of the limits specified in section 95465(a)(2) detected during the annual monitoring that can not be remediated within 10 calendar days will result in a return to quarterly monitoring of the landfill.
(D) Any exceedances of the limits specified in section 95465(a)(2) detected during any compliance inspections will result in a return to quarterly monitoring of the landfill.
(3) An owner or operator of a closed or inactive MSW landfill, or any closed or inactive areas on an active MSW landfill that can demonstrate that in the three years before the effective date of this subarticle that there were no measured exceedances of the limits specified in section 95465 by annual or quarterly monitoring may monitor annually. Any exceedances of the limits specified in section 95465 detected during the annual monitoring that can not be remediated within 10 calendar days will result in a return to quarterly monitoring of the landfill.
(b)Gas Control System Equipment Monitoring: The owner or operator must monitor the gas control system using the following procedures:
(1) For enclosed flares the following equipment must be installed, calibrated, maintained, and operated according to the manufacturer's specifications:
(A) A temperature monitoring device equipped with a continuous recorder which has an accuracy of plus or minus (±) 1 percent of the temperature being measured expressed in degrees Celsius or Fahrenheit.
(B) At least one gas flow rate measuring device which must record the flow to the control device(s) at least every 15 minutes.
(2) For a gas control device other than an enclosed flare, demonstrate compliance by providing information describing the operation of the gas control device, the operating parameters that would indicate proper performance, and appropriate monitoring procedures. Alternatives to this section must be submitted as specified in section 95468. The Executive Officer may specify additional monitoring procedures.
(3) Components containing landfill gas and under positive pressure must be monitored quarterly for leaks. Any component leak must be tagged and repaired within 10 calendar days, or it is a violation of this subarticle.
(A) Component leak testing at MSW landfills having landfill gas-to-energy facilities may be conducted prior to scheduled maintenance or planned outage periods.
(c)Wellhead Monitoring: The owner or operator must monitor each individual wellhead monthly to determine the gauge pressure. If there is any positive pressure reading other than as provided in sections 95464(d) and 95464(e), the owner or operator must take the following actions:
(1) Initiate corrective action within five calendar days of the positive pressure measurement.
(2) If the problem cannot be corrected within 15 days of the date the positive pressure was first measured, the owner or operator must initiate further action, including, but not limited to, any necessary expansion of the gas collection system, to mitigate any positive pressure readings.
(3) Corrective actions, including any expansion of the gas collection and control system, must be completed and any new wells must be operating within 120 days of the date the positive pressure was first measured, or it is a violation of this subarticle.

Cal. Code Regs. Tit. 17, § 95469

1. New section filed 6-17-2010; operative 6-17-2010 pursuant to Government Code section 11343.4 (Register 2010, No. 25).

Note: Authority cited: Sections 38501, 38510, 38560, 38560.5, 38580, 39600 and 39601, Health and Safety Code. Reference: Sections 38501, 38505, 38510, 38550, 38551, 38560, 38560.5, 39003, 39500, 39600 and 39601, Health and Safety Code.

1. New section filed 6-17-2010; operative 6-17-2010 pursuant to Government Code section 11343.4 (Register 2010, No. 25).