The following Rules and Regulations for Hospitals and Related Institutions in Arkansas are duly adopted and promulgated by the Arkansas State Board of Health pursuant to the authority expressly conferred by the laws of the State of Arkansas in Ark. Code Ann. §§ 20-9-201 et.seq., 20-7-123, and other laws of the State of Arkansas.
These rules and regulations have been prepared for the purpose of establishing a criterion for minimum standards for licensure, operation and maintenance of hospitals and related institutions in Arkansas that is consistent with current trends in patient care practices. By necessity they are of a regulatory nature but are considered to be practical minimum design and operational standards for these facilities. These standards are not static and are subject to periodic revisions in the future as new knowledge and changes in patient care trends become apparent. However, it is expected that facilities will exceed these minimum requirements and that they shall not be dependent upon future revisions in these standards as a necessary prerequisite for improved services. Hospitals and related institutions have a strong moral responsibility for providing optimum patient care and treatment for the populations they serve.
The word shall as used in these regulations means mandatory.
The following categories of facilities (G-Q), as defined herein, established for the purpose of providing inpatient diagnostic care and treatment for more than 24 hours for two or more persons not related to the proprietor, may not be conducted or maintained in this state without being licensed.
The following categories (Q-R) of outpatient facilities may not be conducted or maintained in this state without being licensed:
Services in writing at least 30 days prior to the effective date of change of ownership.
NOTE: If services are to be temporarily suspended, afunctional program, with plans and specifications as applicable, shall be submitted to Health Facility Services for approval prior to such suspension.
An institution shall have an organized Governing Body which shall be legally responsible for maintaining quality patient care and establishing policies for the facility. The Governing Body shall be legally responsible for the conduct of the institution.
All persons admitted and discharged to any institution governed by these standards shall be under the care of a person duly licensed to practice medicine in Arkansas (hereafter called physician). In institutions where two or more physicians are allowed to practice there shall be an organized Medical Staff. Members of the staff shall be qualified legally and professionally for the positions to which they are appointed. Individuals who are not hospital employees, who work in the hospital shall be credentialed through the Medical Staff with approval from the Governing Body. (Refer to Section 36, Specialized Services: Emergency Services.)
Note: See Ark. Code Ann. § 17-95-107 regarding requirements for health care organizations that credential physicians/authorized staff to use the Arkansas State Medical Board's Centralized Credentials Verification Service (CCVS).
NOTE: Hospitals shall report to the Arkansas State Medical Board the names of physicians whose hospital privileges have been terminated or revoked for cause.
Each patient admitted to the hospital shall have an identification bracelet applied during the admission process.
Registered Nurse qualified by advanced education and management experience. The nurse executive's education and experience shall be directly related to the facility's stated mission and to the nursing care needs of the patient population.
There shall be an adequate number of Registered Nurses on duty at all times and available for bedside care of any patient when needed on a 24 hour basis. In addition, there shall be sufficient Registered Nurses to staff all patient care units. A Registered Nurse shall assign the nursing care of each patient to other nursing personnel in accordance with the patient's needs and the preparation and competence of the nursing staff. There shall be written criteria to substantiate the assignments.
NOTE: Block charting and cosignatures are not acceptable.
Patients that remain in observation status for a period of 24 hours or more, shall have provided to them accommodations equivalent to the accommodations they would have if they were admitted as an inpatient.
applicable licensed personnel at nursing and specialty units shall maintain the daily security of medications at their respective units.
NOTE: Emergency Room Records shall be completed within 24 hours of the patient's visit.
NOTE: Observation records shall be completed on patients who stay less than 24 hours.
All hospitals shall have adequate provision for pharmaceutical services regarding the procurement, storage, distribution and control of all medications. There shall be compliance with all federal and state regulations, including Laws and Regulations -Arkansas State Board of Pharmacy.
Limited amounts of Schedule II-V controlled substances may be stocked in the machines,
provided the following requirements are met:
The person removing a medication for administration shall record at least the patient's name and the name, strength and amount of medication on a record that is maintained by the Pharmacy Department.
The record shall also be signed by the person removing the medication. The removal of controlled substances shall comply with the record keeping requirements of Section 12, Medications. Pharmacy Services shall audit stock levels as needed to replace medications. Use of the machines shall not be to circumvent adequate pharmaceutical services.
The U.S.P. DI, three book set including "Drug Information for the Healthcare Professional" (two volumes) and "Advice for the Patient" (one volume) Or the two volume set "Facts and Comparisons" (one volume) and "Patient Drug Facts" (one volume);
NOTE: These regulations are referenced to the Rules and Regulations Pertaining
to Food Service Establishments, of the Arkansas Department of Health.
Shall be a registered dietitian, or registry eligible, and evaluate and oversee the delivery of effective nutritional care based on current, recognized nutritional practices. If not full-time, make regularly scheduled visits to accomplish the following:
NOTE: The facility's system for surveillance, calculation and evaluation of the incidence of nosocomial infections within the facility shall conform to CDC's National Nosocomial Infections Surveillance System (NNIS) and CDC publications as applicable.
Mycobacterium tuberculosis (TB). All plans for the prevention of transmission of TB shall conform to the most current CDC Guidelines for Preventing the Transmission of Mycobacterium Tuberculosis in Health Care Facilities;
NOTE: A hospital which provides only limited laboratory services (e.g., blood gas laboratory only) shall not be subject to the requirement of oversight of a pathologist.
trouble-shooting and calibration procedures related to each test performed;
The laboratory shall have documentation of the verification or establishment of all applicable test performance specifications and shall establish control and calibration procedures based upon those specifications.
Blood shall be visually inspected at the time of issue. Results of all inspections shall be recorded.
NOTE: If an electronic signature is used, the laboratory shall ensure that only the authorized person can release the signature. Refer to Section 14, Health Information Services.
Licensed physical therapist means any person licensed to practice physical therapy by the Arkansas State Board of Physical Therapy.
The practice of licensed physical therapy assistants shall be performed under the supervision of the licensed physical therapist. The supervising therapist shall be readily available for consultations, evaluations and establishment of each program prior to delegation of any treatments and determination of patient discharge.
If physical therapy services are rendered by an individual who does not meet at least the assistant-level qualifications (aide/technician), a qualified physical therapist shall be on the premises and immediately available to provide assistance and direction throughout the time the services are rendered.
In facilities with an organized Occupational Therapy Department, the following shall apply:
When appropriate elements are planned and arranged for shared use by physical therapy patients and staff, one or both services shall be responsible for the preventive maintenance program and the retention of records.
In facilities with an organized Speech Language Pathology/Audiology Services Department, the following shall apply:
In facilities with organized Recreational Therapy Services, the following shall apply:
Definitions.
"Program" means Pet Therapy Program.
"Pet" means an animal that has been specifically screened, trained and authorized by the hospital to participate in the Program.
"Handler" means an individual who has been specifically credentialed and authorized by the hospital to participate in, and to accompany and control pets participating in, the Program.
The newborn nursery shall be under the direct supervision of a Registered Nurse with clinical skills in newborn nursing. The newborn nursery shall be located within or adjacent to the postpartum unit. The following requirements shall apply to all nurseries:
A Critical Care Unit is a section of the hospital where intensive care nursing, necessary monitoring and treatment equipment and supplies are provided to those patients who, in the opinion of the attending physician, require such specialized services.
NOTE: All materials sterilized from the date of the biological spore monitor failure to the last successful biological spore monitor shall be resterilized before use.
ALLOWABLE SHELF LIFE | |
Double-wrapped Muslin, Paper or Polypropylene | Use for rapid turn-around items only in well controlled environment, [LESS THAN] 30 days |
Double-wrapped Muslin, Paper or Polypropylene Placed in a Plastic Dust Cover Then Heat Sealed or Bonded | Indefinite |
Peel Pack (Paper, Plastic or Tyvek/Mylar) | Indefinite |
Rigid Containers, Caskets, Etc. | Per Manufacturer's Instructions |
NOTE:
AUTOCLAVE | LOAD | MINIMAL TIME AT TEMPERATURE |
Gravity | Nonporous (Simple Metal Instruments) | 3 minutes at 132ΕC (270ΕF) |
Gravity | Porous (Towels, Rubber, Plastic) Nonporous Mix | 10 minutes at 132ΕC (270ΕF) |
Gravity | Nonporous with Lumens, Deep Grooves, Sliding Parts | 10 minutes at 132ΕC (270ΕF) |
Gravity/Prevacuum | Complex Devices, Air-powered Drills | Per Manufacturer=s Instructions |
Prevacuum | Nonporous | 3 minutes at 132ΕC (270ΕF) |
Prevacuum | Porous/Nonporous | 4 minutes at 132ΕC (270ΕF) |
Items that previously have been packaged, sterilized and issued to the patient care units or other areas where the environment is not controlled shall be discarded if they are single use items, or unwrapped and reprocessed through decontamination if they are reusable.
NOTE: The National Fire Protection Association Vol. 99, Health Care Facilities, is a mandatory reference for developing safety regulations for Respiratory Care Services.
NOTE: Federal EMTALA requirements apply
Medical Service Act Ark. Code Ann. §§ 20-13-201 et.seq., if a hospital allows an Arkansas Certified Emergency Medical Technician to perform specified procedures within the Emergency Room or be a member of a hospital code team the following action shall be taken:
Freestanding Ambulatory Surgery Centers.
The Ambulatory Surgery Center shall have provisions for obtaining prescribed drugs and biologicals to meet the needs of the population served. In addition, policies and procedures shall be developed and implemented for the handling of medications brought into the facility by patients. Should it be necessary to administer a patient's own medications, a signed physician's order shall be in the medical record identifying the medications(s) along with the route and directions for use.
Extended stay may permit patient sleeping accommodations in the post-anesthesia recovery area.
Any facility in which psychiatric services are offered for a period of 4 to 16 hours a day, and where, in the opinion of the attending psychiatrist, hospitalization, as defined in the present licensure law, is not necessary, is considered an Outpatient Psychiatric Facility. This definition does not include Community Mental Health Clinics and Centers as they now exist. Such facilities shall conform with applicable sections if those services are provided within the facility. Such facilities shall conform with applicable sections of Section80, Physical Facilities, Outpatient Care Facilities.
NOTE: May be provided under contract or arrangement on an as needed basis.
Any facility which includes inpatient beds with an organized Medical Staff, and with medical services including physician services and continuous nursing services to provide treatment for patients who are not in an acute phase of illness but who currently require primarily convalescent or restorative services, shall be considered a recuperation center and shall comply with applicable Sections 1, Authority, through 76, Physical Facilities, Electrical Standards.
If the facility does not choose to follow Section 10, Patient Identification, they shall take three pictures of the patient at the time of admission. Pictures shall be attached:
Facilities, Psychiatric Hospitals and Alcohol/Drug Abuse Inpatient Treatment Centers.
An infirmary shall be considered a facility established for the purpose of offering temporary medical care and/or treatment exclusively for persons residing on a designated premise, e.g., schools, reformatories, correctional institutions, etc.
Alcohol/Drug Abuse Inpatient Treatment Center means a facility or distinct part of a facility in which services are provided for the diagnosis, treatment and rehabilitation of alcohol and/or drug abuse; a facility which provides counseling only (room and board are not included in this definition). Participating hospitals shall designate a distinct part and a specific number of beds for the unit. The distinct part unit shall be at least 10 beds, with a maximum of ten percent (10%) of the total hospital licensed capacity recommended. Free-standing facilities shall not be larger than 70 beds or smaller than 35 beds. Each facility or unit shall have the capability of providing for emergency services 24 hours per day, seven days per week. Detoxification beds -alcohol/drug abuse treatment beds which are engaged during that period in which the patient is being physically withdrawn from chemical substances in order that they may be able to participate in rehabilitative activities. Active treatment beds - alcohol/drug abuse treatment beds which are used in providing a highly structured rehabilitative treatment program.
Alcohol/Drug Inpatient Treatment Centers shall comply with the following sections of the Rules and Regulations for Hospitals and Related Institutions in Arkansas:
Alternative consideration: the Means of Egress Requirements for Health Care Occupancies of NFPA 101 (or equivalency per Section 47 of these regulations).
NOTE: Laundry equipment and installation requirements are set forth in Section 68, Physical Facilities, Linen Service.
The facility shall supply for each project (other than a repair project) a functional program that describes the purpose of the project and indicates the estimated cost of construction.
NOTE: See other sections of this document for Special-Care area units such as Postanesthesia Care Unit, Critical Care Units, Rehabilitation Units, Pediatric Units, Postpartum Care Units and/or other specialty units.
The Critical care units require special space and equipment considerations for effective staff functions. In addition, space arrangement shall include provisions for immediate access of emergency equipment from other departments. Critical care units shall comply in size, number and type with these standards and with the functional program. The following standards are intended for the more common types of critical care services and shall be appropriate to needs defined in functional programs. Where specialized services are required, additions and/or modifications shall be made as necessary for efficient, safe, and effective patient care.
In renovation of existing critical care units, every effort shall be made to meet the above minimum standards. If it is not possible to meet the above square foot standards, the Entity having jurisdiction may grant approval to deviate from this requirement. In such cases, rooms shall be no less than 130 square feet.
Normal newborn infants shall be housed in nurseries that comply with the standards below. All nurseries other than pediatric nurseries shall be convenient to the postpartum nursing unit and obstetrical facilities. The nurseries shall be located and arranged to preclude the need for nonrelated pedestrian traffic. No nursery shall open directly into another nursery. There should be one breastfeeding/pumping room readily available for mothers of NICU babies to pump breastmilk.
For hospitals that provide continuing care for infants requiring close observation (for example, low birth-weight babies who are not ill but require more hours of nursing than do normal neonates), the minimum floor space-shall be 50 square feet (4.65 square meters) per bassinet, exclusive of auxiliary work areas, with provisions for at least 4 feet (1.22 meters) between and at all sides of each bassinet.
To minimize the possibility of cross infection, each nursery room serving pediatric patients shall contain no more than eight bassinets; each bassinet shall have a minimum clear floor area of 40 square feet (3.72 square meters). Each room shall contain a lavatory equipped for hands-free handwashing, a nurses emergency calling system and a glazed viewing window for observing infants from public areas and workrooms. (Limitation on number of patients in a nursery room does not apply to the pediatric critical care unit.)
The unit shall meet the following standards:
Provisions shall also be made for storage of equipment and supplies (including cots or recliners, extra linen, etc.) for parents who stay with the patient overnight.
When part of a general hospital, these units shall be designed for the care of inpatients. Non-ambulatory inpatients may be treated in a medical unit until their medical condition allows for transfer to the psychiatric nursing unit. Provisions shall be made in the design for adapting the area for various types of psychiatric therapies.
The environment of the unit should be characterized by a feeling of openness with emphasis on natural light and exterior views. Various functions should be accessible from common areas while not compromising desirable levels of patient privacy. Interior finishes, lighting and furnishings should suggest a residential rather than an institutional setting. These should, however, conform with applicable fire safety codes. Security and safety devices should not be presented in a manner to attract or challenge tampering by patients.
Where glass fragments pose a hazard to certain patients, safety glazing and/or other appropriate security features shall be used.
Details of such facilities should be as described in the approved functional program. Each nursing unit shall provide the following:
Accommodations (Adult Medical, Surgical, Communicable or Pulmonary Disease), shall be applied to patient rooms in psychiatric nursing units except as follows:
The Surgical Suite shall be located and arranged to preclude unrelated traffic through the Suite. The Surgical Suite shall be designed in accordance with NFPA 99 except that, within suites, mixed facilities as defined in NFPA 99 shall not be allowed. The Suite(s) shall provide the following elements.
The endoscopy suite may be divided into three major functional areas: the procedure room(s), instrument processing room(s), and patient holding/preparation and recovery room or area.
NOTE: When invasive procedures are to be performed in this unit on persons who are known or suspected of having airborne infectious diseases, these procedures should not be performed in the operating suite. These procedures shall be performed in a room meeting airborne infections isolation ventilation requirements or in a space using local exhaust ventilation.
Cleaning rooms shall allow for flow of instrumentations from the contaminated area to the clean area, and finally to storage. The clean equipment rooms, including storage, should protect the equipment from contamination.
Handwashing stations with hands-free operable controls shall be available with at least one for every four lounge chairs uniformly distributed to provide equal access from each patient bed.
interviews, testing, and obtaining vital signs. A separate area shall be provided where outpatients may change from street clothing into hospital gowns.
Provisions shall be made for appropriate aeration of supplies. Aeration cabinets shall be vented to the outside. Where aeration cabinets are not used in ethylene oxide processing, provision for isolated area mechanically vented to the outside for aeration, OSHA standards shall be met.
General. The obstetrical unit shall be located and designated to prohibit non-related traffic through the unit. When delivery and operating rooms are in the same suite, access and service arrangements shall be such that neither staff nor patients need to travel through one area to reach the other. Except as permitted otherwise herein, existing facilities being renovated shall, as far as practicable, provide all the required support services.
When a closed cart system is used, the cart shall be stored out of the path of normal traffic.
Where LDRs or LDRPs are not provided, a minimum of two labor beds shall be provided for each Caesarean room and/or delivery room. In facilities that have only one Caesarean/ delivery room, two labor rooms shall be provided. Each room shall be designed for either one or two beds with a minimum clear area of 120 square feet per bed. Each labor room shall contain a handwashing fixture and have access to a private toilet room. One toilet room may serve two labor rooms. Labor rooms shall have controlled access with doors that are arranged for observation from a nurses' station. At least one shower (which may be separate from the labor room if under staff control) for use of patients in labor shall be provided. Windows in labor rooms, if provided, shall be located, draped, or otherwise arranged to preserve patient privacy from causal observation from outside the labor room.
Each LDR or LDRP room shall be for single occupancy and have direct access to a private toilet with shower or tub. Each room shall be equipped with handwashing stations (handwashing stations with hands-free operation area acceptable for scrubbing). Examination lights may be portable, but shall be immediately accessible.
Finishes shall be selected to facilitate cleaning and with resistance to strong detergents. Window(s) shall be provided for LDRP room(s). Windows or doors within a normal sightline that would permit observation into the room shall be arranged or draped as necessary for patient privacy. Additional requirements for windows are provided above in A.2.a.
Hot lab.
These facilities shall be directly accessible to an outside entrance and shall be located to avoid movement of bodies through public areas. The following elements shall be provided when autopsies are performed within the hospital:
NOTE: If autopsies are performed outside the facility, only a well ventilated, temperature-controlled, body-holding room need be provided.
The size and type of services to be provided in the pharmacy can largely depend upon the type of medication distribution system used, number of patients to be served, and extent of shared or purchased services. This shall be described in the functional program. The pharmacy room or suite shall be located for convenient access, staff control, and security. Facilities and equipment shall be as necessary to accommodate the functions of the program. See Section 16, Pharmacy, for additional requirements. (Satellite facilities, if provided, shall include those items required by the program.) As a minimum, the following elements shall be included:
Construction, equipment, and installation shall comply with the standards specified in FDA U.S. Public Health Service Food Code. Food service facilities shall be designed and equipped to meet the requirements of the functional program. These may consist of an onsite conventional food preparing system, a convenience food service system, or an appropriate combination of the two. The following shall be provided:
The following areas shall be provided:
The following rooms and areas shall be provided:
The following areas shall be provided:
Clean/Sterile Medical/Surgical Supplies. A room shall be provided for the breakdown of clean/sterile bulk supplies. Storage for packs etc., shall include provisions for ventilation, humidity, and temperature control.
If required by the functional program, this room shall be separate from all other areas and provide for staff to change from street clothes into work attire. Lockers, sink, and showers shall be made available within the immediate vicinity of the department.
This area shall be adjacent, easily available to clean and sterile storage, and close to main distribution point to keep traffic to a minimum and to ease work flow.
In addition to supply facilities in individual departments, a central storage area shall also be provided. General stores may be located in a separate building onsite with provisions for protection against inclement weather during transfer of supplies. The following shall be provided:
Each facility shall have provisions for storing and processing of clean and soiled linen for appropriate patient care. Processing may be done within the facility, in a separate building on- or off-site, or in a commercial or shared laundry.
Space shall be included in all mechanical and electrical equipment rooms for proper maintenance of equipment. Provisions shall also be made to provide for equipment removal and replacement. The following shall be provided:
All details for alteration or expansion projects as well as for new construction shall comply with the following.
break resistant material that creates no dangerous cutting edges when broken. Similar materials shall be used for wall openings in active areas such as recreation rooms and exercise rooms, unless otherwise required for fire safety. Safety glass-tempered or plastic glazing materials shall be used for shower doors and bath enclosures. Plastic and similar materials used for glazing shall comply with the flame-spread ratings of NFPA 101. Safety glass or plastic glazing materials, as noted above, shall also be used for interior windows and doors, including those in pediatric and psychiatric unit corridors. In renovation projects, only glazing within 18 inches of the floor shall be changed to safety glass, wire glass, or plastic, break-resistant material. NFPA 101 contains additional requirements for glazing in exit corridors, etc., especially in buildings without sprinkler systems.
NOTE: NFPA 101 generally covers fire/safety requirements only, whereas most model codes also apply to structural elements. The fire/safety items of NFPA 101 would take precedence over other codes in case of conflict. In the event NFPA 101 does not specifically address a life safety requirement found only in the Arkansas Fire Prevention Code, compliance with the requirement is not mandatory. Appropriate application of each would minimize problems. For example, some model codes require closers on all patient doors. NFPA 101 recognizes the potential fire/safety problems of this requirement and stipulates that if closers are used for patient room doors, smoke detectors shall also be provided within each affected patient room.
NFPA 101. If a separate underlayment is used with any floor finish materials, the underlayment and the finish material shall be tested as a unit. Tests shall be performed by an approved independent testing laboratory.
NOTE: Additional elevators installed for visitors and material handling may be smaller than noted above, within restrictions set by standards for disabled access.
All plumbing systems shall be designed and installed in accordance with the requirements of the latest edition of the Arkansas State Plumbing Code and the latest edition of the Laws, Rules, and Regulations Governing Boiler Inspection, Arkansas Department of Labor.
The signal shall activate an annunciator panel at the nurse station, a visible signal in the corridor at the patient's door, and at other areas defined by the functional program. Provisions for emergency calls will also be provided in outpatient and treatment areas where patients are subject to incapacitation.
NFPA 101 and NFPA 72.
Helicopter landing area (if provided) shall be documented.
NOTE: If there are wire obstacles, wire markers are available at no charge. They shall be picked up at the Arkansas Department of Aeronautics.
Visual and audible privacy shall be provided by design and include the registration, preparation, examination, treatment, and recovery areas.
When sterilization is provided off site, adequate sterile supplies shall be provided. If onsite processing facilities are provided, they shall include the following:
This room is exclusively for the inspection, assembly, and packaging of medical/surgical supplies and equipment for sterilization and shall contain work tables, counters, ultrasonic cleaning facilities for backup supplies and instrumentation or equipment. The room shall be designed to hold sterilizer carts for loading or prepared supplies for sterilization.
toilets, clothing change or gowning area(s), and space for medication administration. The functional program shall include provisions for securing patients' personal effects.
Laundry Services shall conform to Section 68, Physical Facilities, Linen Service.
Electrical Standards, with the following exceptions:
Mechanical Requirements, with the exception that stand-by fuel requirements shall be eight hours.
.
retardant and shall pass both the large- and small-scale tests required by NFPA 701.
The following standards shall be met for patient dining, recreation, and day spaces (areas may be in separate or adjoining spaces):
Engineering Service and Equipment Areas.
Physical Facilities, Cleaning and Sanitizing Carts and Environmental Services.
TABLE 1
Area Designation | No. Filter Beds | Filter Bed No.1 (%) | 1 Filter Bed No.2 (%) |
All areas for patient care, treatment, and diagnosis, and those areas providing direct service or clean supplies such as sterile and clean processing. | 2 | 30 | 90 |
Protective Environment Room 2 | 2 | 30 | 99.97 |
Laboratories | 1 | 80 | - |
Administrative, Bulk Storage, Soiled Holding Areas, Food Preparation Areas, and Laundries | 1 | 30 | - |
¹These requirements do not apply to small outpatient clinics or outpatient clinics that do not perform invasive applications or procedures.
Notes: The filtration efficiency ratings are based on average dust spot efficiency per ASHRAE 52.1 -1992.
Additional roughing or prefilters should be considered to reduce maintenance required for filters with efficiencies higher than 75 percent.
TABLE 2
Sound Transmission Limitations in Health Care Facilities | ||
Airborne Sound 1 Transmission Class (STC) | ||
Partitions | Floors | |
2 NEW CONSTRUCTION | ||
Patients= Room to Patients= Room | 45 | 40 |
3 Public Space to Patients= Room | 55 | 40 |
4 Service Areas to Patients= Room | 65 | 45 |
5 Patient room access corridor | 45 | 45 |
Exam room to exam room | 45 | |
Exam room to public space | 45 | |
Toilet room to public space | 45 | |
Consultation rooms/ conference rooms to public space | 45 | ____ |
Consultation rooms/ Conference rooms to patient rooms | 45 | ____ |
Staff lounges to patient rooms | 45 | |
2 Existing Construction | ||
Patient room to patient room | 35 | 40 |
3 Public space to patient room | 40 | 40 |
4 Service areas to patient room | 45 | 45 |
1. Sound transmission class (STC) shall be determined by tests in accordance with methods set forth in ASTM Standard E90 and ASTM E413. Where partitions do not extend to the structure above, sound transmission through ceilings and composite STC performance shall be considered.
2. Treatment rooms shall be treated the same as patient rooms
3. Public space includes corridors (except patient room access corridors), lobbies, dining rooms, recreation rooms, treatment rooms, and similar spaces.
4. Service areas include kitchens, elevators, elevator machine rooms, laundries, garages, maintenance rooms, boiler and mechanical equipment rooms, and similar spaces of high noise. Mechanical equipment located on the same floor or above patient rooms, offices, nurses stations, and similar occupied space shall be effectively isolated from the floor.
5. Patient room access corridors contain composite walls with doors/windows and have direct access to patient rooms.
TABLE 3
Temperature and Relative Humidity Requirements | ||
Area Designation | Dry Bulb Temperatures ºF¹ | Relative Humidity (%) Minimum-Maximum² |
Operating Rooms, Delivery Rooms, Endoscopy, and Bronchoscopy | 68-73 | 30-60 |
Newborn Intensive Care and Newborn Nursery Suite | 72-78 | 30-60 |
Recovery, Intensive Care, Trauma Rooms, Procedure Rooms, and Radiological X-ray (Surgical/Critical Care and Catheterization) | 71-75 | 30-60 |
Clean Work Room and ETO Sterilizer Room | 75 | 30-60 |
Sterile Storage | 75 | 70 (max) |
¹Where temperature ranges are indicated, the systems shall be capable of maintaining the rooms at any point within the range. A single figure indicates a heating or cooling capacity of at least the indicated temperature. This is usually applicable when patients may be undressed and require a warmer environment. Nothing in these guidelines shall be construed as precluding the use of temperatures lower than those noted when the patients= comfort and medical conditions make lower temperatures desirable. Unoccupied areas such as storage rooms shall have temperatures appropriate for the function intended.
2Humidification systems serving anesthetizing locations shall be designed in accordance with NFPA 99 paragraph 5-4.1.1.
TABLE 4
Ventilation, Medical Gas, and Air Flow Requirements in Health Care Facilities1
Area Designation | Air Movement Relationship To Adjacent Area | Minimum Air Changes Outside Air Per Hour3 | Minimum Total Air Changes Per Hour4,5 | Air Recirculated By Means of Room Unit7 | All Air Exhausted Directly Outdoor6 |
SURGERY AND CRITICAL CARE AREAS | |||||
Operating/Surgical Cystoscopic Rooms 8,9 | Out | 3 | 15 | No | Optional |
Delivery Room 8 | Out | 3 | 15 | No | Optional |
Recovery Room8 | - | 2 | 6 | No | Optional |
Critical Care and Intensive Care | - | 2 | 6 | No | Optional |
Newborn intensive care | - | 2 | 6 | No | Optional |
Treatment Room 10 | - | - | 6 | Optional | Optional |
Trauma Room10 | Out | 3 | 15 | No | Optional |
Anesthesia gas storage | In | - | 8 | Optional | Yes |
Endoscopy | In | 2 | 6 | No | Optional |
Bronchoscopy 9 | In | 2 | 12 | No | Yes |
ER Waiting Room | In | 2 | 12 | No | Yes 11,12 |
Triage | In | - | 12 | No | 11 Yes |
Radiology waiting rooms | In | 2 | 12 | Optional | 11, 12 Yes |
Procedure room | Out | 3 | 15 | No | Optional |
NURSING AREAS | |||||
Patient Room | - | 2 | 13 6 | Optional | Optional |
Toilet Room | In | - | 10 | Optional | Yes |
Newborn Nursery Suite | - | 2 | 6 | No | Optional |
Protective environment room 9,14 | Out | 2 | 12 | No | Optional |
Airborne Infectious Isolation, Bronchoscopy 9, 15 Room | In | 2 | 12 | No | Yes |
14,15 Isolation alcove or anteroom | In/Out | - | 10 | No | Yes |
Labor/Delivery/Recovery (LDR) | - | 2 | 13 6 | Optional | Optional |
Labor/Delivery/ Recovery/ Post Partum (LDRP) - | - | 2 | 613 | Optional | Optional |
Patient Corridor | - | - | 2 | Optional | Optional |
ANCILLARY AREAS | |||||
Radiology X-ray (Surgical/Critical Care & 16 Catheterization) | Out | 3 | 15 | No | Optional |
Radiology X-ray (Diagnostic & Treatment)16 | - | - | 6 | Optional | Optional |
Radiology Darkroom | In | - | 10 | No | Yes |
l6 Lab General | - | - | 6 | Optional | Optional |
16 Lab Biochemistry | Out | - | 6 | No | Optional |
Lab Cytology | In | - | 6 | No | Yes |
Lab Glass Washing | In | - | 10 | Optional | Yes |
Lab Histology | In | - | 6 | No | Yes |
Lab Microbiology 16 | In | - | 6 | No | Yes |
Lab Nuclear Med | In | - | 6 | No | Yes |
Lab Pathology | In | - | 6 | No | Yes |
Lab Serology | Out | - | 6 | No | Optional |
Lab Sterilizing | In | - | 10 | Optional | Yes |
Autopsy9 | In | - | 1712 | No | Yes |
Nonrefrigerated body holding room | In | - | 10 | Optional | Yes |
Pharmacy | Out | - | 4 | Optional | Optional |
DIAGNOSTIC AND TREATMENT AREAS | |||||
Examination Room | - | - | 6 | Optional | Optional |
Medication Room | Out | - | 4 | Optional | Optional |
Treatment Room | - | - | 6 | Optional | Optional |
Physical Therapy and Hydrotherapy | In | - | 6 | Optional | Optional |
Soiled Workroom or Soiled Holding | In | - | 10 | No | Yes |
Clean Workroom or Clean Holding | Out | - | 4 | Optional | Optional |
STERILIZING AND SUPPLY AREAS | |||||
ETO Sterilizer Room | In | - | 10 | No | Yes |
Sterilizer Equipment Room | In | - | 10 | Optional | Yes |
Central Supply Soiled or Decontamination Room | In | - | 6 | No | Yes |
Central Supply Clean Workroom17 | Out | - | 4 | No | Optional |
Sterile Storage | Out | - | 4 | Optional | Optional |
SERVICE AREAS | |||||
Food Preparation Centers17 | - | - | 10 | No | Optional |
Warewashing | In | - | 10 | No | Yes |
Dietary Day Storage | In | - | 2 | Optional | Optional |
Laundry, General | - | - | 10 | Optional | Yes |
Soiled Linen Sorting and Storage | In | - | 10 | No | Yes |
Clean Linen Storage | Out | - | 2 | Optional | Optional |
Soiled Linen and Trash Chute Room | In | - | 10 | No | Yes |
Bedpan Room | In | - | 10 | Optional | Yes |
Bathroom | In | - | 10 | Optional | Optional |
Janitor's Closet | In | - | 10 | No | Yes |
Notes for Table 4
1. The ventilation rates in this table cover ventilation for comfort, as well as for asepsis and odor control in areas of acute care hospitals that directly affect patient care and are determined based on healthcare facilities being predominantly "No Smoking" facilities. Where smoking may be allowed, ventilation rates will need adjustment. Areas where specific ventilation rates are not given in the table shall be ventilated in accordance with ASHRAE Standard 62, Ventilation for Acceptable Indoor Air Quality; and ASHRAE Handbook-HVAC Applications. Specialized patient care areas, including organ transplant units, burn units, specialty procedure rooms, etc., shall have additional ventilation provisions for air quality control as may be appropriate. OSHA standards and/or NI0SH criteria require special ventilation requirements for employee health and safety within healthcare facilities.
2. Design of the ventilation system shall provide air movement which is generally from clean to less clean areas. If any form of variable air volume or load shedding system is used for energy conservation, it shall not compromise the corridor-to-room pressure balancing relationships or the minimum air changes required by the table. Where the air movement relationship is "In " (negative) or "Out" (positive), the air movement relationship shall not be reversible. Rooms with reversible airflow provision for the purpose of switching between "In" and "Out" are not acceptable.
3. To satisfy exhaust needs, replacement air from the outside is necessary. Table 4 does not attempt to describe specific amounts of outside air to be supplied to individual spaces except for certain areas such as those listed. Distribution of the outside air, added to the system to balance required exhaust, shall be as required by good engineering practice. Minimum outside air quantities shall remain constant while the system is in operation.
4. Number of air changes may be reduced when the room is unoccupied if provisions are made to ensure that the number of air changes indicated is reestablished any time the space is being utilized. Adjustments shall include provisions so that the direction of air movement shall remain the same when the number of air changes is reduced. Areas not indicated as having continuous directional control may have ventilation systems shut down when space Is unoccupied and ventilation is not otherwise needed, if the maximum infiltration or exfiltration permitted in Note 2 is not exceeded and if adjacent pressure balancing relationships arc not compromised. Air quantity calculations shall account for filter loading such that the indicated air change rates are provided up until the time of filter change-out.
5. Air change requirements indicated are minimum values. Higher values should be used when required to maintain indicated room conditions (temperature and humidity), based on the cooling load of the space (lights, equipment, people, exterior walls and windows, etc.).
6. Air from areas with contamination and/or odor problems shall be exhausted to the outside and not recirculated to other areas. Note that individual circumstances may require special consideration for air exhaust to the outside, e.g., in intensive care units in which patients with pulmonary infection are treated, and rooms for burn patients.
7. Recirculating room HVAC units refers to those local units that are used primarily for heating and cooling of air, and not disinfection of air. Because of cleaning difficulty and potential for buildup of contamination, recirculating room units shall not be used in areas marked "No." However, for airborne infection control, air may be recirculated within Individual isolation rooms if HEPA filters are used. Isolation and intensive care unit rooms may be ventilated by reheat induction units in which only the primary air supplied from a central system passes through the reheat unit. Gravity-type heating or cooling units such as radiators or convectors shall not be used m operating rooms and other special care areas. See Appendix A for a description of recirculation units to be used in isolation rooms.
8. National Institute for Occupational Safety and Health (NIOSH) Criteria Documents regarding Occupational Exposure to Waste Anesthetic Gases and Vapors, and Control of Occupational Exposure to Nitrous Oxide indicate a need for both local exhaust (scavenging) systems and general ventilation of the areas in which the respective gases are utilized.
9. Differential pressure shall be a minimum of 0.01" water gauge (2.5 Pa). If alarms are installed, allowances shall be made to prevent nuisance alarms of monitoring devices.
10. The term trauma room as used here is the operating room space in the emergency department or other trauma reception area that is used for emergency surgery. The first aid room and/or "emergency room" used for initial treatment of accident victims may be ventilated as noted for the "treatment room." Treatment rooms used for Bronchoscopy shall be treated as Bronchoscopy rooms. Treatment rooms used for cryosurgcry procedures with nitrous oxide shall contain provisions for exhausting waste gases.
11. In a ventilation system that recirculates air, HEPA filters can be used in lieu of exhausting the air from these spaces to the outside. In this application, the return air shall be passed through the HEPA filters before it is introduced into any other spaces.
12. If it is not practical to exhaust the air from the airborne infection isolation room to the outside, the air may be returned through HEPA filters to the air-handling system exclusively serving the isolation room.
13. Total air changes per room for patient rooms, labor/delivery/recovery rooms, and labor/delivery/recovery/postpartum rooms may be reduced to 4 when supplemental heating and/or cooling systems (radiant heating and cooling, baseboard heating, etc.) are used.
14. The protective environment airflow design specifications protect the patient from common environmental airborne infectious microbes (i.e., Aspergillus spores). These special ventilation areas shall be designed to provide directed airflow from the cleanest patient care area to less clean areas. These rooms shall be protected with HEPA filters at 99.97 percent efficiency for a 0.3 micron sized particle in the supply airstream. These Interrupting filters protect patient rooms from maintenance-derived release of environmental microbes from the ventilation system components. Recirculation HEPA filters can be used to increase the equivalent room air exchanges. Constant volume airflow is required for consistent ventilation for the protected environment. It the facility determines that airborne infection isolation is necessary for protective environment patients, an anteroom shall be provided. Rooms with reversible airflow provisions for the purpose of switching between protective environment and airborne infection isolation functions are not acceptable.
15. The infectious disease isolation room described in these guidelines is to be used for isolating the airborne spread of infectious diseases, such as measles, varicella, or tuberculosis. The design of airborne infection isolation (All) rooms should include the provision for normal patient care during periods not requiring Isolation precautions. Supplemental recirculating devices may be used in the patient room, to increase the equivalent room air exchanges; however, such recirculating devices do not provide the outside air requirements. Air may be recirculated within individual isolation rooms if HEPA filters are used. Rooms with reversible airflow provisions for the purpose of switching between protective environment and All functions are not acceptable.
16. When required, appropriate hoods and exhaust devices for the removal of noxious gases or chemical vapors shall be provided per NFPA 99.
17. Food preparation centers shall have ventilation systems whose air supply mechanisms arc interfaced appropriately with exhaust hood controls or relief vents so that exfiltration or infiltration to or from exit corridors does not compromise the exit corridor restrictions of NFPA 90A, the pressure requirements of NFPA 96, or the maximum defined in the table. The number of air changes may be reduced or varied to any extent required for odor control when the space is not in use.
TABLE 5
Final Occupancy Inspection Check List
TABLE 6
Behavioral Screening Exam
TABLE 7
TABLE 8
RECORD RETENTION TIME FRAMES
DEPARTMENT | DOCUMENT | RETENTION TIME |
Administrative | Governing Body | Permanent |
Medical Staff | Permanent | |
Executive Committees | Permanent | |
Other Hospital Committees | 2 years | |
Medical Records | Original/Microfilm Adult/Inpatient/Outpatient Electrocardiogram Strips/ Interpretations Electroencephalogram/ Interpretations | 10 years after last discharge. Facility shall maintain information in the master patient index. |
Original/Microfilm Minor/Inpatient/Outpatient Fetal Monitor Strips Electroencephalogram/ Interpretations Electroencephalogram/ Interpretations | 10 years after last discharge plus 2 years past majority. Facility shall maintain information in the master patient index. | |
Radiology | Films | 5 years |
Nuclear Medicine | Films | 5 years |
Laboratory | Blood Gas Reports | 2 years |
Patient Specimens | 2 years | |
Control Documentation | 2 years | |
Immunohematology | 5 years | |
Immunohematology Quality Control Records | 5 years | |
Cytology: Histopathology Quality Control Records | 10 years | |
Transfusions | 5 years | |
Blood Donor Samples | 7 days post transfusion | |
Quality Assurance | 2 years | |
Pathology Lab | Pathology Reports | 10 years |
Reference Pathology | 2 years | |
Preliminary/Corrected | Exact duplicate | |
Histopathology | Stained Slides | 10 years |
Specimen Blocks | 2 years | |
Pharmacy | All drug records to include: Purchase invoices Official records Prescription records Inventory records, etc | 2 years |
TABLE 9
REQUIRED TEMPERATURES
MEDICATIONS | Refrigerators | 36-46 ºF |
Medication Storage Room | 59-86 ºF | |
1 DIETARY | Temperature of Food at Bedside | Hot Foods =[GREATER THAN]140ºF |
Cold Foods =[LESS THAN]40ºF | ||
Temperature of Heated Food Prior to Hot Holding | [GREATER THAN]160 ºF | |
Temperature of Heated Leftovers Prior to Hot Holding | [GREATER THAN]165ºF | |
Temperature for Thawing Potentially Hazardous Food | Tempering Units = 45ºF or less | |
Refrigerator = 40ºF or less | ||
Refrigerators | [LESS THAN]40ºF | |
Freezers | [LESS THAN]0ºF | |
Single Tank Stationary Rack Dual Temperature Machine | Wash Temperature = 150ºF Final Rinse Temperature = 180ºF | |
Single Tank Conveyor Machine | Wash Temperature = 180ºF | |
Final Rinse Temperature = 180ºF | ||
Multi-tank Conveyor Machine | Wash Temperature = 150ºF | |
Final Rinse Temperature = 180ºF | ||
Pumped Rinse Temperature = 160ºF | ||
Single Tank Pot, Pan & | Wash Temperature = 140ºF | |
Utensil Washer | Final Rinse Temperature = 180ºF | |
Manual Warewashing | Wash Temperature = 110ºF | |
Rinse Temperature = 120ºG - 140ºF | ||
Chemical Sanitation (Manual or Mechanical) | Sanitation Temperature = *171ºF or Immersion in 75ºF water and 50 ppm of hypochlorite for at least 1 minute or other method approved by Arkansas Department of Health | |
All Cutting Board Surfaces | Immersion in clean, hot water of * 180ºF for at least 30 seconds or any other method approved. | |
LAUNDRY2 | Water | Nothing under 120ºF |
Water with Chlorine Bleach | 150 parts per million ppm (parts per million) | |
CLINICAL | Gallons per hour per bed2 | 105ºF - 120ºF |
Notes for Table 9:
1. Provisions shall be made to provide 180°F rinse water at warewasher. (may be by a separate booster.)
2. Provisions shall be made to provide 160°F hot water at the laundry equipment when needed. (This may be a steam jet or separate booster heater.) However, this does not imply that all water used would be at this temperature. Water temperatures required for acceptable laundry results will vary. Lower temperatures may be adequate for most procedures in many facilities but the higher 160°F should be available when needed for special conditions.
TABLE 10
Newborn Screening Requirements
All Newborns shall be tested for: | |||
1. Newborn Hearing Screening | |||
2. Newborn Genetic Screening: | |||
PKU Phenylketonuria | CH Congenital Hypothyroidism | Galactosemia | Sickle Cell Anemia* |
For further Information Arkansas Department of Health, Child & Adolescent Health Team | |||
Contacts: Newborn Lab Screening: 501-661-2592 | |||
Newborn Hearing Screening: 501-661-2459 |
Note: Lab specimens should be mailed promptly to prevent degradation of the specimen and increase the quality of results.
Reference: Ark. Code Ann. 20-15-302,304 Ark. Code Ann. 20-15-1104 Ark. Code Ann. 20-15-1504
*Non-Caucasians
TABLE 11
Central6 Station Outlets for Oxygen, Vacuum (Suction), and Medical Air Systems in Hospitals1
Patient Rooms (medical & surgical) | 1/bed | 1/bed | - |
Examination/Treatment (medical, surgical, endoscopy & postpartum care) | 1/room | 1/room | - |
Isolation -Infectious and protective medical & surgical) | 1/bed | 1/bed | - |
Security Room (medical, surgical, & postpartum) | 1/bed | 1/bed | - |
Critical Care (general) | 3/bed | 3/bed | 1/bed |
Isolation (critical) | 3/bed | 3/bed | 1/bed |
Coronary Critical Care | 3/bed | 2/bed | 1/bed |
Pediatric Critical Care | 3/bed | 3/bed | 1/bed |
Newborn Intensive Care | 3/bassinet | 3/bassinet | 3/bassinet |
Newborn Nursery (full-term) | 1 / 4 bassinets2 | 1 / 4 bassinets2 | 1 / 4 bassinets2 |
Pediatric and Adolescent | 1/bed | 1/bed | 1/bed |
Pediatric Nursery | 1/bassinet | 1/bassinet | 1/bassinet |
Psychiatric Patient Rooms | - | - | - |
Seclusion Treatment Room | - | - | - |
General Operating Room | 2/room | 3/room | - |
Cardio, Ortho, Neurological | 2/room | 3/room | - |
Orthopedic Surgery | 2/room | 3/room | - |
Surgical Cysto & Endo | 1/room | 3/room | - |
Post-anesthesia Care Unit | 1/bed | 3/bed | 1/bed |
Anesthesia Workroom | 1 per workstation | - | 1 per workstation |
3 Phase II Recovery | 1/bed | 3/bed | - |
Postpartum Bedroom | 1/bed | 1/bed | - |
Cesarean/Delivery Room | 2/room | 3/room | 1/room |
4 Infant Resuscitation Station | 1/bassinet | 1/bassinet | 1/bassinet |
Labor Room | 1/room | 1/room | 1/room |
OB Recovery Room | 1/bed | 3/bed | 1/room |
5 Labor/Delivery/Recovery (LDR) | 2/bed | 2/bed | - |
5 Labor/Delivery/Recovery (LDRP) | 2/bed | 2/bed | - |
Initial Emergency Management | 1/bed | 1/bed | - |
Triage Area (definitive emergency care) | 1/station | 1/station | - |
Definitive Emergency Care Exam/Treatment Rooms | 1/bed | 1/bed | 1/bed |
Definitive Emergency Care Holding Area | 1/bed | 1/bed | - |
Trauma/Cardiac Room(s) | 2/bed | 3/bed | 1/bed |
Orthopedic & Cast Room | 1/room | 1/room | - |
Cardiac Catheterization Lab | 2/bed | 2/bed | 2/bed |
Autopsy Room | - | 1 per workstation | 1 per workstation |
Notes for Table 11
1. For any area or room not described above, the facility clinical staff shall determine outlet requirements after consultation with the authority having jurisdiction.
2. Four bassinets may share one outlet that is accessible to each bassinet.
3. If Phase II recovery area is a separate area from the PACU, only one vacuum per bed or station shall be required.
4. When infant resuscitation takes place in a room such as cesarean section/delivery or LDRP, then the infant resuscitation services shall be provided in that room in addition to the minimum service required for the mother.
5. Two outlets for mother and two for one bassinet.
6. Facilities with medical gas requirements in more than one area shall be equipped with central systems.
TABLE 12 VERBAL ORDER
Basic Premise: | Verbal orders may be used when there is no reasonable alternative to obtaining a written order. |
State Health Rules: | Permit licensed nurses and pharmacist (for drugs only) to take verbal orders and no one else. Section 12, Medications and Section 14, Health Information Services. |
Practical Application: | Health professionals other than nurses may take verbal orders pertaining directly to their profession under specified circumstances. |
Situation to Address: | 1. Doctor in the department away from nurses station. 2. Doctor calls the department. |
Policy Statement Parts: | 1. Who are the authorized receivers? 2. Repeat order back for accuracy. 3. Identify ordering doctor. 4. Identify receiver by name and title. 5. The receiver of the order shall enter the order on the medical record, and then sign first initial, last name and title. |
Hospital Administration Responsibility: | 1. Policy shall be in writing, and approved by the Medical Staff and Governing Body (including identification of receivers). 2. Policy shall be made a part of applicable department manuals. 3. Inservice training provided for all personnel involved. 4. Establish an effective monitoring system. |
Outpatient Department (Emergency Services is not outpatient): | 1. The therapist or other authorized receivers may take a verbal or telephone order from the doctor. 2. Shall document on outpatient medical record. 3. Doctor shall authenticate the order on his next visit. |
RATIONALE
Health Facility Services has received numerous requests for a variance in the regulations relating to who may receive doctors orders for hospital inpatients and outpatients. This office realizes the communication problems involved between every expanding service departments of hospitals and the multiplicity of diagnostic treatment, therapy, and therapeutic duties necessary for coordinating of patient care. Other certification and accrediting organizations have also realized the communication difficulty.
The reason and intent of the regulation was, and still is, to coordinate all inpatient care through nursing service. The patient's medical record shall be maintained at the nurses station to coordinate and implement physician orders for patient care and services.
It is the intent of this policy to have both communication between departments and also assure all physician orders and services rendered to patients are promptly documented on the patient's chart. In order to maintain continuity of care on an inpatient basis, it is necessary that all aspects of the patients' treatment be coordinated through the nursing service of the facility.
TABLE 13 REUSE
THIRD PARTY REPROCESSING OF SINGLE USE ITEMS
The Office of Compliance Center of Devices and Radiological Health of the Food and Drug Administration (FDA) provides guidelines for third party reprocessing of devices labeled for single use provided the reprocessing firm complies fully with all FDA regulatory requirements.
The Arkansas Department of Health will recognize FDA guidelines.
CERTIFICATION
This will certify that the foregoing revisions to the Rules and Regulations for Hospitals and Related Institutions in Arkansas were adopted by the State Board of Health of Arkansas at a regular session of said Board held in Little Rock, Arkansas, on the 26th day of July, 2007.
____________________________________
Paul Halverson, DrPH. Date
Executive Officer, Arkansas State Board of Health, State Health Officer
The forgoing Rules and Regulation, copy having been filed in my office, are hereby approved.
____________________________________
Mike Beebe Date
Governor
016.24.07 Ark. Code R. 003