Ariz. Admin. Code § 18-5-502

Current through Register Vol. 30, No. 45, November 8, 2024
Section R18-5-502 - Minimum Design Criteria
A. A public water system shall be designed using good engineering practices. A public water system which is designed in a manner consistent with the criteria contained in Engineering Bulletin No. 10, "Guidelines for the Construction of Water Systems," issued by the Arizona Department of Health Services, May 1978 (and no future editions), which is incorporated herein by reference and on file with the Office of the Secretary of State, shall be considered to have been designed using good engineering practices. Other system designs shall be approved if the applicant can demonstrate that the system will function properly and may be operated reliably in compliance with this Chapter. Minimum design criteria which are not subject to modification are listed in this Section.
B. A potable water distribution system shall be designed to maintain and shall maintain a pressure of at least 20 pounds per square inch at ground level at all points in the distribution system under all conditions of flow.
C. Water and sewer mains shall be separated in order to protect public water systems from possible contamination. All distances are measured perpendicularly from the outside of the sewer main to the outside of the water main. Separation requirements are as follows:
1. A water main shall not be placed:
a. Within 6 feet, horizontal distance, and below 2 feet, vertical distance, above the top of a sewer main unless extra protection is provided. Extra protection shall consist of constructing the sewer main with mechanical joint ductile iron pipe or with slip-joint ductile iron pipe if joint restraint is provided. Alternate extra protection shall consist of encasing both the water and sewer mains in at least 6 inches of concrete for at least 10 feet beyond the area covered by this subsection (C)(1)(a).
b. Within 2 feet horizontally and 2 feet below the sewer main.
2. No water pipe shall pass through or come into contact with any part of a sewer manhole. The minimum horizontal separation between water mains and manholes shall be 6 feet, measured from the center of the manhole.
3. The minimum separation between force mains or pressure sewers and water mains shall be 2 feet vertically and 6 feet horizontally under all conditions. Where a sewer force main crosses above or less than 6 feet below a water line, the sewer main shall be encased in at least 6 inches of concrete or constructed using mechanical joint ductile iron pipe for 10 feet on either side of the water main.
4. The separation requirements do not apply to building, plumbing, or individual house service connections.
5. Sewer mains (gravity, pressure, and force) shall be kept a minimum of 50 feet from wells unless the following conditions are met:
a. Water main pipe, pressure tested in place to 50 psi without excessive leakage, is used for gravity sewers at distances greater than 20 feet from water wells; or
b. Water main pipe, pressure tested in place to 150 psi without excessive leakage, is used for pressure sewers and force mains at distances greater than 20 feet from water wells. "Excessive leakage" means any amount of leakage which is greater than that permitted under the AWWA Standard applicable to the particular pipe material or valve type.
6. Requests for authorization to use alternate construction techniques, materials, and joints shall be reviewed by the Department, and such requests may be approved on a case-by-case basis.
D. A public water system shall not construct or add to its system a well which is located:
1. Within 50 feet from existing sewers unless the sewer main has been constructed in accordance with subsection (C)(5)(a) or (b) of this Section;
2. Within 100 feet of any existing septic tank or subsurface disposal system;
3. Within 100 feet of a discharge or activity which is required to obtain an Individual Aquifer Protection Permit, pursuant to A.R.S. §§ 49-241(A) through 49-251;
4. Within 100 feet of an underground storage tank as defined in A.R.S. § 49-1001; or
5. Within 100 feet of hazardous waste facilities operated by large quantity generators and treatment, storage, and disposal facilities regulated under the Arizona Hazardous Waste Management Act, A.R.S. § 49-921 et seq.

Ariz. Admin. Code § R18-5-502

Section recodified from R18-4-502 at 10 A.A.R. 585, effective January 30, 2004 (Supp. 04-1).