Ariz. Admin. Code § 14-2-2624

Current through Register Vol. 30, No. 50, December 13, 2024
Section R14-2-2624 - Disconnect Switch Requirements
A. If required by a Utility, a Customer shall install and maintain a visual-open, manually operated, load break Disconnect Switch that completely opens and isolates all ungrounded conductors of the Generating Facility from the Distribution System. For multi-phase systems, the Disconnect Switch shall be gang-operated.
B. A Utility may impose additional requirements for a Disconnect Switch in its Interconnection Manual.

Ariz. Admin. Code § R14-2-2624

Adopted by final rulemaking at 26 A.A.R. 473, effective 2/25/2020.